14/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
Step
Section
Description
5
3.1
Create new plant
Workflow:
1.
Plant > New > Plant….
.
2. Enter plant name.
3. Describe plant (optional).
4. Select unit type "OZW775" in "Communication" dialog box.
5. Keep code number 01 and interface "USB".
6. Refresh device list, click
Yes
.
7. Open
the
[Popcard]
via
Applications > Popcard…
.
8. Expand menu tree and check devices in the folder list.
Does the folder list contain all desired device = Yes / No:
Yes
Continue at step 7
No
Continue at step 6
Note:
−
After you create a new plant, the central communication unit is in "Commissioning
mode = On" (not normal operation). Carry out the next steps under "Commissioning
mode = On".
6
3.2
Edit device list
3.2.1 Create
device
list
"Create device list" is always required after creating a new plant.
Workflow:
1. Select
Plant > Edit device list…
.
2. Right-click
Device address 150
(= central communication unit) to open the context
menu and then select
Create device list
.
3. Check the devices in the "List of assigned devices".
Does the folder list contain all desired device = Yes / No:
Yes
Continue at step 7
No
Devices from other lines/areas are missing; see "Add devices"
No
List contains unwanted devices; see "Delete devices"
Note:
−
Command
Create device list
creates and displays the "List of assigned devices". The
list contains the central communication unit and the devices integrated in the line (or
area) of the central communication unit.
3.2.2
Add devices
Needed to add devices from other lines and/or areas.
Prerequisite:
Plant > Edit device list…
already selected.
Workflow:
1. Right-click the "List of assigned devices" field to open the context menu and then
select
Add devices…
.
2. The "Add device" dialog box opens. Click
Add device
.
3. The "Add/change device" dialog box opens. Enter the address values.
4. Click
Add
to confirm the entered address values.
5. Add the device(s) to the device list by clicking
Write device list
in the "Insert
devices" dialog box.
6. Close
the
ACS operation – [Edit device list]
dialog box.
7. Select
Applications > Popcard…
to open the
[Popcard]
and check if the device list
contains the device(s).