Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
Step
Section
Description
8
4.2
Central communication unit data points
4.2.1
Examples for data point value changes
−
Select the data point and double-click it to open the dialog box.
−
Change the values and click
OK
to enter the changed value.
4.2.2
Data point description
−
The following are displayed: Default value, setting value(s) and explanations.
4.2.3
Inputs/outputs, function blocks, interfaces
−
The terminal and function block inputs/outputs play a key role in parameterization.
See below for data points of the operating page "Commissioning" > "Extra
configuration".
9
4.3
Application [ Parameter Setting ]
4.3.1
Data points in the "Commissioning" operating page
Command sequence:
Data points
Commissioning > Basic configuration
Basic
configuration
> Extra configuration > Input identifier
N.X1…N.X8
> Time switch
[Time switch 1…4] relay
[Time switch 1…4] op selector
> Meter
Input 1…8
Displayed
unit
Displayed
format
> Operating hours
Input 1...5.
> Faults
Fault button external
Fault input 1…20
Fault
relay
1…2
> Message receiver
Message inhibition
4.3.2
Data points in the "Settings" operating page
Command sequence:
Data points
Settings
> Central communication unit
Language
Code
> Time of day/date
Time synchronization
Time
zone
Mains
frequency
> Communication
> Konnex
Decentral bus power supply
Clock time mode Konnex
Remote setting clock slave
Konnex
> Ethernet
IP address
IP subnetwork address
Default
gateway
DNS server 1
DNS server 2
UPnP
localization
MAC address (read-only)
Address mail server
Port number mail server
E-mail address sender
Authentication mail server
User
name
Password
> USB
UPnP localization
> Modem
Modem type
Fax
protocol
Baud rate RS-232
Command abortion connection
Reset
command
Initialization
command
Command opening connection
Command
closure
Modem message interval