17/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
Step
Section
Description
9
(continued)
4.3
Application [ Parameter Setting ]
4.3.2
Data points in the "Settings" operating page
Command sequence:
Data points
Settings
> Message receiver
> Message receiver 1
Message receiver 1
Receiver
type
Interface*)
Transmission
protocol
Fault
priority
address
Address ACS alarm
Port number ACS alarm
Message
repetition
Phone number receiver
Phone number provider
Hardware
settings
Display
format
Service
number
Receiver key word
> Message receiver
> Message receiver 2..3
same as Message receiver 1
*)
Data points in italics are displayed depending on the data point configuration for "Receiver type",
"Interface", "Modem type", "Transmission protocol".
Command sequence:
Data points
Settings
> System report
Signal time
Message
cycle
Fault
priority
> Inputs
> N.X1
N.X1
Normal position *)
Text for: Logic 0
Text for: Logic 1
Type
Correction
Value
low
Value
high
> Inputs
> N.X2...8
same as N.X1
*)
Data points in italics are displayed depending on the data point configuration for "Input identifier".
Command sequence:
Data points
Settings
> Inputs
> N.D1
N.D1
Normal
position
Text for: Logic 0
Text for: Logic 1
> N.D2…8
same as N.D1
> Time switches
Time switch 1…4
[Time switch 1…4] Invert. Relay
Command sequence:
Data points
Settings
> Meter *)
> Meter 1.
Meter 1
Pulse
unit
Pulse valency numerator
Pulse valency denominator
Overflow
value
> Meter 2…8
same as Meter 1
> Operating hours**) > Operating hours 1
Operating hours 1
Service
interval
Message
triggering
Text for: Service required
Text for: Service done
> Operating hours 2…5
same as Operating hours 1
*)
The command sequences Meter >Meter 1…8 (Pulse meter 1…8) and the corresponding data
points are displayed only if e.g. data point "N.X4 = Pulse" was parameterized via Extra
configuration > Input identifier, and e.g. data point "Input 4 = N.X4" via Extra configuration > Meter.
**) The command sequences Operating hours > Operating hours 1…5 (Hours run counter 1…5) and
the corresponding data points are displayed only if e.g. data point "Input 5 = N.D5" was
parameterized via Extra configuration > Operating hours".