18/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
Step
Section
Description
9
(continued)
4.3
Application [ Parameter Setting ]
Data points in the "Settings" operating page
Command sequence:
Data points
Settings
> Faults
> Local
> Central commun. unit
Message triggering
> Local *) > Fault input 1
Fault input 1
Limit value fault on
Limit value fault off
Fault status message delay
Fault
acknowledgement
Fault
priority
Message
triggering
Text for: No fault
Text for: Fault
> Fault input 2…20
same as Fault input 1
*)
The command sequences Local >Fault input 1…20 and the corresponding data points are displayed
only if e.g. data point "N.X2 = Digital" was parameterized via Extra configuration > Input identifier,
and e.g. data point "Fault input 2 = N.X2" via Extra configuration > Faults.
4.3.2
Command sequence:
Data points
Settings
> System
Message triggering
> Fault relay
> Fault relay 1
Fault priority
Fault
source
> Fault relay 2
same as Fault relay 1
>
Texts
Name
Phone
number
4.3.3
Data points in the "Time switches" operating page
Command sequence:
Data points
Time switches
> Time switch 1
Monday
…
Sunday
> Time switch 2….3
same as Time switch 1
4.3.4
Data points in the "Message receiver" operating page
Command sequence:
Data points
Message receiver
> Message receiver 1
> Send messages
(time switch) Monday *)
…
(time switch) Sunday
(time switch) special day
> Holidays/special days
Entry 1…16
Message receiver > Message receiver 2…4 > Send messages
same as Message receiver 1
*) The command sequences and data points are displayed only if you preconfigured the data point
"Receiver type" (and other data points) via "
Settings
> Message receiver > Message
receiver 1".
10
4.4
Download parameter set
Finish central communication unit parameterization (Step 9) with "Write parameter
set". Parameterization can be offline.
Workflow:
1. Establish a connection to the plant before selecting
Write parameter set
.
2. Select the data points you want to download.
3. Right-click the parameter set (e.g.
Standard(1)
) to open the context menu and select
Write parameter set
.
4. Click
Write parameter set
to start the write process (writing progress is displayed).
5. Check transmission: The "Transmission result" column must show OK.
Note:
−
Parameterization is not yet complete. Continue in application [ Popcard ]
"Commissioning mode = On".
−
Applications [ Parameter Setting ] and [ Popcard ] display the same data points in
the "Settings" operating page.