Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Recommended commissioning
22.06.2012
2.5 Web server function
2.5.1 Prepare web server data
Web server data must be prepped fro all central communication units to be operated as
web servers. Thus, for:
•
Original central communication units V1.0
with firmware update V2.0.
•
Central communication unit V2.0.
You must order the CF card OZZ7CF with the latest web server data (and the latest
firmware) separately.
Do not switch off AC 24 V operating voltage while preparing data!
See also the supplied installation instructions G5663xx (multi-lingual).
Prerequisites:
•
The central communication unit must be connected to the PC/laptop via USB
(RNDIS driver must be installed on the PC/laptop).
•
Start the web browser and enter IP address
192.168.250.1
. The web browser
displays the following:
Insert the CF card in the upper slot "CF Card Memory".
Press "Config" button "long" >4 seconds to integrate the CF card. Preparation then
starts automatically.
Preparation is completed when all LEDs "Run" and "CF Cards" are lit. See Section
2.5.2 "First login in the web browser".
56
63Z
20
1
Insert CF card
face up
56
63Z
18
Push button "Config" >4 sec.
2
56
63Z
19
Wait until LEDs "Run"
and "CF Cards" light up
3
Note:
Keep the CF card in the upper slot "CF Card Memory" for web server
operation.
Important notes
Prepare
web server data
G2
.
G2