51/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
Expand the menu items
Commissioning
and
Extra configuration
, then:
•
Select menu item
Input identifier
.
•
Double-click data point
N.X3
to open the "Data point command" dialog box.
•
Select the desired value from the "Actual value" field, e.g. °C, if universal input
N.X3 is used for temperature sensors.
•
Click
OK
to enter the new value.
4.2.2 Data point description
The following pages briefly describe the data points. See Section 1.3 for the meaning of
symbols and abbreviations in the tables. The following are displayed:
•
Default value
•
Setting value(s)
•
Explanation, example
•
Data point (DP)
•
Reference data point (ref DP)
•
User level
The setting values in the following tables are based on "Basic configuration = Basic
type Z" (see following page, first table).
The central communication unit's data points are described in the order in line with
commissioning steps.
Application [ Parameter Setting ]
Section 4.3
Application [ Popcard ] "Commissioning mode = On"
Section 4.6
Application [ Popcard ] "Commissioning mode = Off"
1)
Section 4.7
1)
Application [ Popcard ] "Commissioning mode = Off" corresponds to normal mode in the central
communication unit.
Example 2:
Data point N.X3