64/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
Example: Modem type = GS
1.
Applications > Parameter Setting…
.
Command sequence: Settings > Communication > Modem.
2. Parameterization reference data point "Modem type = GSM".
After you parameterize the modem type, you must also parameterize the message
receiver.
Data points of "Message receiver" (receiver 1…4), see next pages.
Example: Message receiver 1 for SMS to mobile phone.
1.
Applications > Parameter Setting…
Command sequence:
Settings > Message receiver > Message receiver 1 (SMS 1).
2. Parameterize reference data points:
Receiver type = Mobile phone
Interface =
Modem
3. Parameterize the other data points or keep the default values:
Message receiver 1
= SMS 1 (new name, free selectable info text)
Transmission protocol
= SMS GSM (as per modem type)
Fault priority
= All
Message repetition
= 3
Phone number receiver
= Number of mobile phone
Select the telephone service provider and modem depending on the message receiver.
If you use a GSM modem, make sure the SIM card allows for data communication and
is not protected by a PIN code.
Parameterize modem
type
Workflow
Note
Parameterize message
receiver
Workflow
Important note