65/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
Command sequence: Settings > Message receiver > Message receiver 1…4
Data point
Explanation, example
Message receiver 1…4
Default val: (Blank)
Setting val: Name
Ref. DP "Message receiver 1" (1…4) allows for
entering the name (text) with max. 20
alphanumeric characters.
The name is displayed as information text in
ACS and in messages.
–
Receiver type
Default val: ---
Setting val: ---
ACS
alarm*
Mobile
phone
E-mail
Fax
machine.
Pager
Ref. DP "Receiver type" allows you to configure
the type of message receiver. The following
data points depend on the setting value:
"Interface" (USB, modem, Ethernet) and,
depending on "Interface", the "Modem type" and
the "Transmission protocol".
Setting value "---" does not determine the
receiver type, i.e. the message receiver is
inactive.
–
Interface
Default val: USB
Setting val: USB
Modem
Ethernet*
Setting value USB / Modem / Ethernet connects
the receiver (FB "Message receiver", receiver
1…4) to the corresponding interface.
–
Transmission protocol
Default val: ACS protocol
Setting val: ACS protocol
UCP
TAP
SMTP
SMS
GSM,
SMS GSM service
Fax
protocol
The setting value depends on the data point
configuration for "Modem type", "Receiver type",
and "Interface". See the setting values for data
point "Transmission protocol" in the table below.
–
* ACS alarm via Ethernet from ACS CD V5.10
Receiver type
Interface
Modem type
1)
Transmission protocol
--- (Default)
-
-
-
Ethernet
xx
SMTP
USB
xx
Modem Analog/ISDN
GSM
ACS alarm
Ethernet
2)
xx
ACS protocol
Analog/ISDN
TAP
UCP
Mobile phone
Modem
GSM
SMS GSM
Analog
Fax protocol
GSM Fax
protocol
Fax
Modem
SMS GSM service
Analog/ISDN
TAP
GSM TAP
Pager
Modem
SMS GSM service
1) Modem type, see command sequence: Settings > Communication > Modem.
2) ACS alarm via Ethernet from ACS CD V5.10
No
other
selection
-
Value cannot be set
or no value entry required.
xx
No modem required.
Italics/Bold
Default value.
Example: Receiver
type
= E-mail.
Interface
= Ethernet (Default if receiver type = E-mail).
Transmission
protocol
=
SMTP
(Default if receiver type = E-mail).
Message receiver 1…4