66/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
Command sequence: Settings > Message receiver > Message receiver 1…4
Data point
Explanation, example
Fault priority
Default val: All
Setting val: All, Only urgent
faults
Setting value "Only urgent faults" serves as a
filter when sending fault status messages.
–
Data point "E-mail address" is displayed if:
•
Receiver type
•
Interface
= Ethernet
•
Transmission protocol = SMTP
Data point
Explanation, example
E-mail address
Default val:
name@example.com
Setting val: E-mail address
The setting value (max. 20 characters) must
correspond to the e-mail address of the
receiver, e.g. PC/laptop with e-mail reception.
–
Data points "Address ACS alarm" and "Port number ACS alarm" are displayed if:
•
Receiver type
= ACS alarm
•
Interface
= Ethernet
•
Transmission protocol
= ACS protocol
Data point
Explanation, example
Address ACS alarm
Default val: acs.example.com
Setting val: Name / IP address
The setting value (max. 20 characters) must
correspond to the name or IP address of the
ACS alarm receiver, i.e. the PC/laptop with the
installed program "ACS Alarm".
–
Port number ACS alarm
Default val: 49194
Setting val: 1…65535
The setting value must correspond to the port
number of program "ACS Alarm" ("ACS Alarm"
installed on PC/laptop).
–
Data points "Message repetition" and "Phone number receiver" are displayed if:
•
Receiver type
= ACS alarm / mobile phone / fax / pager
•
Interface
= Modem
•
Modem type
= Analog / ISDN / GSM
•
Transmission protocol
= ACS protocol / TAP / UCP / SMS GSM
Data point
Explanation, example
Message repetition
Default val: 3
Setting val: None, 1, 2, 3,
Unlimited
Setting value "None" attempts to send the
pending message once, and setting values "n"
(n = 1, 2, 3) attempt sending n+1 times.
–
Phone number receiver
Default val: (Blank)
Setting val: Phone number
The setting value corresponds to the phone
number of the receiver (e.g. mobile phone) that
is to receive messages (fault, maintenance
messages, system reports).
The default value (blank) means no default
phone number ex works.
Characters allowed: 0…9, /, -, w, W, =, @, !, &,
<, space and comma ' , '
–
Message receiver 1…4
continued