75/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
Command sequence: Settings > Text
Data point
Explanation, example
Name
Default val: OZW775
Setting val: Name
Name (text) with max. 20 alphanumeric
characters. The name is displayed as
information text in ACS and messages.
–
Phone number
Default val: (leer)
Setting val: Text
Phone number (text) with max. 20 alphanumeric
characters.
The number and/or text is displayed as
information text in messages.
–
4.3.3 Data points in the "Time switches" operating page
Command sequence: Time switches > Time switch 1…4
Data point
Explanation, example
Monday…Sunday
Default val: No switching times:
continuously
Off
Setting val: 00:00…24:00
Resolution
00:10
Up to three switching times on/off can be
programmed for each weekday at each time
switch 1…4 (FB "7-day time switch 1…4").
The times are programmed graphically(see
screenshot below).
If switching times were entered for a particular day, that day (screenshot, Tuesday) can
be copied to other days with the same profile.
Texts
Time switch 1…4