82/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
4.7 Application [ Popcard ]
Commissioning mode = Off
Application [ Popcard ] "Commissioning mode = Off" is used for normal operation.
This application displays the data points as needed for normal operation access.
These, for example, are data points for acknowledgement and device information.
4.7.1 Data points in the "Faults current" operating page
Command sequence: Faults current > Local
Data point
Explanation, example
Acknowledge faults
Default val: No
Setting val: Yes
Setting value "Yes" acknowledges faults of type
"Local" (same effect as "Ack" button).
Setting value "Yes" is a temporary state, i.e. the
setting value automatically goes to "No" after ca.
2 seconds.
Command sequence: Faults current > System > Most severe bus fault
Data points
Explanation, example
See box to the right
Setting val: Read-only
Command "Most severe bus fault" displays the
following data points (read-only):
Device name, Fault information, Fault text, Area,
Line, Device address, Device type, Fault
message will be delivered.
See Section 5.5.2 on "Most severe bus fault".
–
Command sequence: Fault current > System > Fault 1…10
Data points
Explanation, example
See box to the right
Setting val: Read-only
Command "Fault 1…10" displays the following
data points (read-only):
Device name, Fault information, Fault text, Area,
Line, Device address, Device type.
See Section 5.5.2 on "Fault 1…10".
–
Normal operation
Local
Most severe bus fault
Fault 1…10