85/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Parameterize OZW775
22.06.2012
Command sequence: Device information > Konnex
Data point
Explanation, example
Number of devices max
Default val: 250
Setting val: Read-only
The data point is read-only.
Note: Value = 250 applies to software version
(firmware) V2.02.
–
Number of devices current
Default val: 0…250
Setting val: Read-only
The data point is read-only.
Note: The number depends on the project,
whereby the number of devices on the KNX
network is indicated without central
communication unit.
–
Last change
Default val: Weekday, Date
Time
Setting val: Read-only
The data point is read-only.
Note: The value displayed comprises weekday,
date and time, e.g. Wednesday March, 26,
2008, 17:34, indicating that the device list was
changed at that point in time.
–
4.7.4 Data point "Time of day/date"
Data point "Time of day/date" is displayed multiple times and can be set in the following
applications:
[ Popcard ] "Commissioning mode = On"
Operating page "Commissioning"
[ Popcard ] "Commissioning mode = Off"
Operating page "Commissioning"
[ Popcard ] "Commissioning mode = Off"
Operating page "Time / Date"
Data point
Explanation, example
Time of day/date
Default val:
Monday, 1 January 2005 00:00
Setting val: Date / Time
The setting values are derived from the current
time (clock time) and the current date.
See Section 5.4.1 on "Time of day and date".
Konnex