HVAC Products
Further commissioning steps
22.06.2012
5.3 Test message receiver
5.3.1 Communication to the message receiver
Use "Commissioning mode On / Off" to test communication with message receivers.
Messages are sent immediately and not repeated during the tests.
Test communication to the message receivers connected via USB, modem, or Ethernet
via "Settings > Message receiver".
1. Select
Applications > Popcard…
command sequence: Settings > Message receiver.
2. Double-click "Test message receiver" to open the data point.
3. Select "Message receiver 2" and click
OK
to enter the value (Message
receiver 2 as an example).
4. Check data point for "System report sent = Yes".
If the message receiver could not be reached, "System report sent = No" is displayed
briefly, followed by "---".
In this case, check the connection to the message receiver via the settings for the
selected interface.
Workflow
Note