98/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Further commissioning steps
22.06.2012
5.5 Final
steps
5.5.1 Check "Local" faults
Faults in the central communication unit and/or at fault inputs.
•
Select
Applications > Popcard…
command sequence: Faults current > Local.
•
Check for "No fault"; see "Value" column in screenshot.
If there are more than 10 faults, fault no. 11, etc., is displayed only after one of the first
10 faults is corrected. Order:
1. Most severe "Local" fault
2. Urgent "Local" faults
3. Not urgent "Local" faults
After commissioning, the red LED "Local" on the central communication unit must not
be lit.
"Local" faults
Fault 1…10
Note
Important note