Installation Instructions

Peligro

Tensión peligrosa
Puede causar daños serio o la
muerte.

Desenergice totalmente antes de
instalar o darle servicio.
Reemplace todas las barreras y
cubiertas antes de  energizar el
interruptor.

Instructivo de Instalación y Operación

Hazardous voltage.
Will cause death or serious
injury.

Turn off and lock out all power
supplying this device before
removing cover or device and while
cover is removed.

Replace the cover before power
supplying this device is turned on.

Page

 

2 of 4

     Pc. No.

 

77503A03

Fig. 3

Fig. 2

C. Device must be in "Tripped" or "OFF" position prior to

mounting.

D. To mount the device perform the following steps:

1. For individual enclosures, panelboards and switch-

boards manufactured by Siemens Energy & Automation,
Inc., follow the instructions provided with this equipment.

2. For those applications where mounting is on a flat sur-

face of the customers equipment, drill and tap mount-
ing bolt holes according to the drilling plan in Fig. 2.

NOTE:  Additional holes marked “A” are required
for types CJD6(-A), CLD6(-A), CJD6(-A) ETI, CLD6(-A)
ETI and CJD6(-A), CLD6(-A) switches. For handle es-
cutcheon cut out plans, refer to Fig. 3.

3. If device contains internal accessories, make sure ter-

minals can be connected when the circuit breaker is
mounted.

4.  Remove the line and load terminal shields (see Fig. 4)

by loosening the two terminal shield screws that at-
tach them to the line and load covers.

5. Position device on mounting surface.

6. Install mounting screws and washers. Tighten hard-

ware securely.

[MANIJA]

4.40 in.

9.75 in.

6.86 in.

2.50 in.

OF HANDLE
ESCUTCHEON

3.14 in.

1.57 in.

2.30 in.

1.50 in.

1.02 in.

3.00 in.

.300 in.[7.6 mm]

DIA. HOLE FOR

ACCESS TO

PUSH-TO-TRIP

C.

Antes de instalar; asegúrese que  la posición de la manija este
en la posición “tripped” disparado o en “OFF” fuera.

D.

Para la instalación del interruptor favor de considerar lo
siguiente.

1.

 Seguir las instrucciones dadas con el suministro de este

equipo, para su instalación en tableros de distribución o
gabinetes recomendados por Siemens SA de CV.

2.

 Para aquellos casos donde el montaje es sobre una superficie

plana, perforar y roscar como indica la fig.2 y para el
escotillón de la manija cortar como indica la fig. 3.

3.

 Si el interruptor contiene accesorios, cerciórese que las

terminales puedan conectarse cuando el interruptor este
instalado.

4

. Remover cubiertas terminales como indica fig. 4.

5.

 Colocar el interruptor sobre la superficie de montaje.

6.

 Colocar y apretar firmemente la tornillería y rondanas contra

la estructura de montaje.

.300Ø perforación

para el acceso al
botón de disparo

[247.6 mm]

[111.8 mm]

[63.5 mm]

[174.2 mm]

[79.8 mm]

[39.9 mm]

[190.5  mm]

[25.9 mm]

[38.1 mm]

[76.2 mm]

OF HANDLE
ESCUTCHEON

DRILL AND TAP
HOLE FOR M6
FASTENERS
(4 PLACES)

[PERFORAR]

1.25 in.

[31.7 mm]

“A”

“A”

[MANIJA]

OF TRIP BUTTON

[boton de disparo]

OF HANDLE ESCUTCH-

EON

[de escotillon de manija]

OF HANDLE ESCUTCH-

EON

[de escotillon de manija]

Summary of Contents for TC1J6600

Page 1: ...Y INSTRUCTIONS Siemens Energy Automation Inc Bellefontaine OH 43311 U S A Installation Instructions Interruptores termomagnéticos Marco JD Tipo JXD2 A JD6 A JXD6 A HJD6 A HJXD6 A HHJD6 HHJXD6 y CJD6 A Marco LD Tipo LD6 A LXD6 A HLD6 A HLXD6 A HHLD6 HHLXD6 y CLD6 A Interruptores Tipo JXD6 A ETI CJD6 A ETI LXD6 A ETI y CLD6 A y Interruptores mobibles Tipo JXD2 A JXD6 A HJXD6 CJD6 A LXD6 A HLXD6 A y ...

Page 2: ...o terminal shield screws that at tach them to the line and load covers 5 Position device on mounting surface 6 Install mounting screws and washers Tighten hard ware securely MANIJA 4 40 in 9 75 in 6 86 in 2 50 in OF HANDLE ESCUTCHEON 3 14 in 1 57 in 2 30 in 1 50 in 1 02 in 3 00 in 300 in 7 6 mm DIA HOLE FOR ACCESS TO PUSH TO TRIP C Antes de instalar asegúrese que la posición de la manija este en l...

Page 3: ... 4 0 500 kcmil Al See Instructions 500 500 500 300 300 300 56 49 56 49 56 49 33 89 33 89 33 89 228 228 228 132 132 132 25 76 25 76 25 76 14 91 14 91 14 91 TABLE 1 7 After mounting the device line and load terminals and accessory terminals should be connected 8 After the device is installed check all mounting hard ware for secureness Check wire connectors for cor rect torque requirements Torque val...

Page 4: ...w any petroleum based chemi cals solvents or paints to contact the molded parts or name plates Circuit breakers in service should be inspected periodically as outlined in NEMA AB2 National Electrical Manufactures Association 2101 L Street N W Suite 300 Washington D C 20037 3 Operación manual La operación de cierre y apertura del interruptor se efectúa por medio de la manija y con el botón pulsador...

Reviews: