background image

3

Operating Characteristics:

The given characteristics (Fig. 6) are average values of all 
ranges and sizes of bimetal relays and are mainly intended 
to indicate the inverse time current characteristics of the 

Operation:

•  Rotate the Latch away from OFF push button
•  For starting the motor, press Green push button marked ‘I’ 

(Fig. 1)

•  For stopping the motor press Red push button marked ‘O’ 

(Fig. 1)

•  This is in ‘Self-Reset’ mode. In this mode even, if the 

relay trips on overload, it will be automatically reset in a 
maximum of 4 minutes. The motor can be restarted only 
after the relay is reset.

Maintenance:

•  Switch off the starter and disconnect the main supply by 

switching the main switch before doing any maintenance.

•  Keep the interior dust free.
•  Re-tighten the terminal screws from time to time.
•  No maintenance is needed for overload relay. Please do 

not open the relay.

•  Replace the contactors / contacts of the contactors if they 

were severely pitted or when only 40% of the original 
contact tips remains.

Fig. 6: Operating characteristics of 3UW51/52 relays

same. The tripping times of the same. The tripping times 
shown are for relays starting from the cold state. At operating 
temperatures (heated at rated current) these are reduced to 
about 25% of the value obtained from the characteristics.

•  Replacement of Overload Relay (Refer Fig. 7):

 

 Removal

  1.  Disconnect the wires connected to the relay terminals.
  2.  Slightly loosen the outgoing terminal screws of the line 

contactor.

  3.  Follow instructions given in Fig. 7 for removal of relay.

  –  Re-fixing

  1.  Select & take the overload relay of same range.
  2.  Connect the relay terminals (L1, L2, L3) to (T1, T2, T3) 

of Q1 Line contactor.

  3.  Refer Fig. 7 for details.
 

Care should be taken to fix the relay terminals & relay 
to contactor in the exact position shown in Fig. 7

  4.  Ensure that relay hook is engaged at contactor housing 

slot at base.

  5.  Tighten the contactor terminal screws.
  6.  Re-connect the disconnected wires and check 

connections by referring to the wiring diagram.

Summary of Contents for TE7291-0A Series

Page 1: ... ON operation of Starter Fig 1 ASD 11 Starter Connect outgoing cables on the Relay K1 terminals and Delta contactor Q3 terminals Tightening torque N cm kW Ratings Incoming Terminals Outgoing Terminals 7 5 11 80 140 80 140 15 18 5 150 210 100 150 Connect the earthing conductor to terminals marked earth on the starter body with torque 80 to 140 N cm The Starter is now ready for commissioning Initial...

Page 2: ...ctions Fig 4 Maximum permissible mounting position from vertical plane Fig 5 Timer Adjustment Commissioning Read the note carefully before commissioning Start the motor and let it run for 30 mins Then gradually reduce the relay settings till it trips Set the relay at a slightly higher value than this setting Restart the motor after some time If the relay does not trip then consider it to be proper...

Page 3: ...of the contactors if they were severely pitted or when only 40 of the original contact tips remains Fig 6 Operating characteristics of 3UW51 52 relays same The tripping times of the same The tripping times shown are for relays starting from the cold state At operating temperatures heated at rated current these are reduced to about 25 of the value obtained from the characteristics Replacement of Ov...

Page 4: ...5 25 38 5 22 2 3TS33 00 0A 08K 3TS33 00 0A 08K 3TS32 10 0A 08K 3UW52 02 2C 16 25 3KL812 50 10 4 Code for operating coil voltage 50 Hz Z6 for 200 400V R0 for 415V Other Tables Star Delta Timer AC Input Voltage MLFB 230V 400V 380V 440V 3RP15 76 1NP20 8K 3RP15 76 1NM20 8K Other Tables Motor Output at 415V Type4 kW HP ASD Starter 7 5 10 3TE72910AW74 9 3 12 5 3TE72910A 75 11 15 3TE72910A 77 15 20 3TE72...

Page 5: ...Notes ...

Page 6: ...sembling and separation into following materials METALS Segregate into Ferrous types for recycling through authorized dealer PLASTICS Segregate as per material type for recycling through authorized dealer Because of the long lifetime of Siemens Products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local customer care service is av...

Reviews: