background image

Technical Instructions 
Document Number 155-066P25 
October 26, 2010 
 

Page 10 

 

Siemens Industry, Inc. 

 

Troubleshooting 

Before troubleshooting thermostat per Table 4, make certain there is clean dry supply air 
at 18 psi (124 kPa) for cooling and 25 psi (172 kPa) for heating. Use test probe gauge 
and needle adapter to measure control pressure at thermostat test port. 

The output pressure test port is accessible without removing the thermostat cover 
through the 8th opening from the top left side for two-pipe thermostats.  

Table 3.  Troubleshooting Guide. 

Problem Check 

Cause 

Action 

Air supply 

Low supply 

pressure 

As required 

Nozzle or 

flapper 

Dirt on nozzle or 

flapper 

Clean nozzle or 

replace thermostat 

Restrictor Clogged 

restrictor Replace 

restrictor 

Control pressure 

stays at 

approximately 

zero 

Calibration 

Out of calibration Recalibrate 

Nozzle Clogged 

nozzle Clean nozzle or 

replace thermostat 

Control pressure 

stays at 

approximately 

supply pressure

Calibration 

Dirt on either supply 

or exhaust valve 

seat 

Alternately close and 

open nozzle by gently 

pushing down the 

bimetal 

 

 

 

Figure 9.  Accessing Output 

Pressure Test Port. 

Excessive air 

leakage from 

exhaust port on 

left side of 

thermostat 

Supply and 

return line 

connection 

Connections are 

interchanged or 

connection to port is 

incorrect 

As required 

 

Chassis

 

Tube 

Connector and 
Restrictor Plate 
Replacement

 

1.  Remove thermostat chassis from wall. Terminal does not have a ball check valve.  

NOTE: 

You must close off the supply air. For example, use a connector with the supply air 
terminal plugged.  

2.  Remove two Phillips head screws from connector on back of thermostat chassis. Pull 

connector out of recess. If necessary, pry connector loose with a screw driver, but be 
careful not to damage restrictor plate and gasket.  

3.  Remove gasket from under connector. Remove restrictor. Remove second gasket from 

under restrictor.  

4.  Use restrictor replacement kit 192-321 to replace gasket, restrictor, and second gasket. 

NOTE: 

The restrictor plate is keyed to ensure proper orientation during installation.  

5.  Remove filters from existing connector and insert in new connector. Or, if filters are 

dirty, use restrictor replacement kit 192-321 to replace filters.  

6.  Use chassis tube connector replacement kit 192-525 to replace connector and mounting 

screws. 

Summary of Contents for TH 192 HC

Page 1: ... chassis for retrofit applications or with plug in adapters provided with the TH 192 rough in terminal box or optional accessories which slide into the wall mounting plate Features Direct and reverse acting models for heating and cooling modes Separate adjustable temperature setpoint indicating dials for heating and cooling Fahrenheit or Celsius setpoint dials Highly sensitive bimetal thermostatic...

Page 2: ...imum economy and occupant comfort automatically as seasons change from the heating setpoint 65 68 F 10 20 C to the cooling setpoint 76 80 F 24 27 C TH 192 HC thermostats are available with covers that conceal or expose the setpoint adjustment dials Figure 1 Typical TH 192 HC Thermostat Application Piping TO CONTROLLED DEVICES AIR SUPPLY R1 S TH 192 HC 2 PIPE THERMOSTAT TH0256R1 Figure 2 TH 192 HC ...

Page 3: ...tpoint adjustment cover or key type cover See Table 2 Covers See Table 2 for product number and ordering information on TH 192 HC thermostat covers 1 Is the setpoint adjustment exposed for customer adjustment or concealed to prevent alteration of setting 2 Is the thermometer exposed or concealed 3 Is the setpoint indication exposed or concealed behind cover 4 Is a plastic or zinc cast metal cover ...

Page 4: ...t knobs 2 To order a plastic cover with white finish add the W suffix code To order a metal cover with a white finish add the H suffix code Specifications Control action See Table 1 Operating ranges 45 to 85 F 7 to 30 C Supply air pressure maximum 30 psi 207 kPa Normal air supply pressure Heating 25 psi 172 kPa Cooling 18 psi 124 kPa Sensitivity adjustment 1 to 4 psi F 12 to 50 kPa C Nominal air c...

Page 5: ...rect or reverse acting cooling control In direct acting control an increase in temperature increases the control air pressure and a decrease in temperature decreases the control pressure In reverse acting control an increase in temperature decreases the control air pressure and a decrease in temperature increases the control pressure The TH 192 HC provides two separate bimetal elements one for hea...

Page 6: ...gauge or manometer to measure supply pressure to thermostat Use 30 psi 207 kPa supply through a positioning switch so pressure can be fully variable 2 Determine current change over point Turn cooling dial so cooling and heating control pressures are different Then note the changeover point on the control gauge as the supply pressure changes 3 Remove thermometer for access to changeover adjustment ...

Page 7: ...een the setpoint cam gear teeth Rotate limit stop to its new position Do not pull limit stop any more than necessary to clear the gear teeth Changing the limit stop position one gear tooth changes the limit stop setting by 1 1 3 F 0 7 C Figure 7 TH 192 HC Limit Stop Adjustments Sensitivity Adjustment To change thermostat sensitivity use a flat blade screwdriver to carefully move the sensitivity sl...

Page 8: ...ng Calibration Step 1 Remove cover using 192 632 calibration tool Verify room temperature is between 70 and 80 F 21 and 27 C Step 2 Verify that supply pressure is 18 psi 124 kPa Set cooling dial to room temperature by turning the exposed adjustment knob or using a hex key as shown Allow thermostat to stand for about five minutes to adjust to the new setting Step 3 Moisten needle and insert 192 633...

Page 9: ... room temperature by turning the exposed adjustment knob or using a hex key as shown Allow thermostat to stand for about five minutes to adjust to the new setting Step 3 Moisten needle and insert 192 633 test gauge and needle adapter in the test port Read control pressure Step 4 If control pressure does not read 7 to 8 psi 48 to 55 kPa turn calibration screw using 192 632 calibration tool or 1 8 3...

Page 10: ...y gently pushing down the bimetal Figure 9 Accessing Output Pressure Test Port Excessive air leakage from exhaust port on left side of thermostat Supply and return line connection Connections are interchanged or connection to port is incorrect As required Chassis Tube Connector and Restrictor Plate Replacement 1 Remove thermostat chassis from wall Terminal does not have a ball check valve NOTE You...

Page 11: ...ck connected 1 8 NPT male 142 0373 1 1 2 diameter compound gauge 0 30 psig 0 200 kPa bottom connected 1 8 NPT male Replacement for use with 192 633 142 0426 Chassis tube connector replacement kit with mounting screws material for 10 thermostats included 192 525 Restrictor plate replacement kit with filters and gasket material for 10 thermostats included 192 321 Plug in adapters for quick thermosta...

Page 12: ...e IL 60089 4513 USA Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Service Parts Continued Description Part Number Replacement thermometer kits brown packages of 5 Scale Range Thermostat Model 45 to 85 F 192 775 10 to 30 C TH0443R1 Model 3 and Up 192 776 45 to 85 F 192 786 10 to 30 C TH0442R1 Models 1 and 2 192 ...

Reviews: