Technical Instructions
Document Number 155-066P25
October 26, 2010
Page 4
Siemens Industry, Inc.
Table 2. TH 192 HC Thermostat Cover Part Numbers.
Cover Configuration
Cover Part Number
(See Note 2)
Setpoint
Adjustment
Thermometer
Setpoint
Indicator
Standard
Plastic Cover
Desert Beige
Standard
Metal Cover
Desert Beige
Concealed 192-256
192-356
Concealed
Exposed
Concealed
192-254 192-354
Concealed 192-267
192-367
Key
(See Note 1)
Exposed 192-268
192-368
Concealed 192-258
192-358
Exposed
Exposed
Exposed
192-260 192-360
1. Key setpoint adjustment cover required for all thermostat chassis with
optional 1/2” large setpoint adjustment knobs.
2. To order a plastic cover with white finish, add the "W" suffix code. To order a
metal cover with a white finish, add the "H" suffix code.
Specifications
Control action
See Table 1.
Operating ranges
45 to 85°F (7 to 30°C)
Supply air pressure, maximum
30 psi (207 kPa)
Normal air supply pressure
Heating
25 psi (172 kPa)
Cooling
18 psi (124 kPa)
Sensitivity adjustment
1 to 4 psi/°F (12 to 50 kPa/°C)
Nominal air consumption (two-pipe)
25 scim (6.8 ml/sec)
Temperature
Storage temperature
-10 to 140°F (-23 to 60°C)
Ambient operating temperature
40 to 140°F (4 to 60°C)
Temperature response
0.1°F (0.06°C)
Dial graduations
2°F (1°C)
Factory settings
Calibration @ 72°F (22°C)
7.5 psi (52 kPa)
Sensitivity
2.5
psi/
°
F (31 kPa/
°
C)
Limit stop adjustment
45 and 85°F (7 and 30°C)
Standard cover
Cycolac, Desert Beige
Shipping weight
0.7 lbs. (0.3 kg)
Dimensions
See Figure 3.