Installation, connecting up, commissioning
3.5 Commissioning
TIM 1531 IRC
48
Operating Instructions, 02/2018, C79000-G8976-C468-02
NOTICE
Only remove / insert the SD card when the power is off
You can only remove or insert the SD card when the TIM is not supplied with power.
If you remove or insert the SD card during operation, data on the card can be damaged.
Inserting the SD card
1.
Insert the SD card into the compartment until you can feel the card lock in place.
Removing the SD card
1.
By pressing, unlock the card.
2.
After unlocking it takes the card out of the slot.
3.5
Commissioning
Requirement
Requirements for commissioning the TIM are as follows:
●
The TIM is mounted and connected up.
●
The TIM is fully configured in STEP 7, refer to the section Configuration (Page 51).
●
The STEP 7 project with the TIM is open on the engineering station.
●
For loading, the engineering station is connected to an Ethernet interface of the TIM.
Downloading the configuration data
To start productive operation the TIM requires the STEP 7 configuration data.
To download the configuration data, follow the steps outlined below:
1.
Change the switch of the TIM to the RUN setting.
2.
Turn on the power supply to the TIM.
The TIM starts up with the factory defaults and remains standing with a yellow flashing
RUN LED.
You will find information on the LED displays during startup in the section Startup - LED
3.
Start by downloading the configuration data.
You will find more detailed information on loading in the following sections of the STEP 7
information system:
●
“Loading project data"
●
“Using online and diagnostics functions"
On completion of the download close the front cover of the TIM.