Configuration
4.7 WAN settings of the interfaces
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
63
4.7
WAN settings of the interfaces
WAN parameters of interfaces
In this parameter group of the interfaces you will find parameters that decide the properties
of the connected WAN network: First, configure the respective interface of the TIM. The
subsequently connected WAN network adopts the most important settings (see below).
●
WAN type
Selection of the WAN type of the interface:
–
IP-based
Default setting of the Ethernet interface
–
Classic WAN
Default setting of the serial interface
To use MSC via GPRS, the serial interface can be changed to "IP-based".
●
Network type
For classic WAN:
–
Dedicated line
–
Dialup network
For IP-based WAN:
–
Neutral
–
Mobile wireless with VPN
–
MSC
●
Connection mode
Decides the Network node type of the interface:
–
Master station
–
Node station
For TIM modules that act as node stations, the following applies:
The interface in the direction of the master station is configured as a "node station".
The interface in the direction of a lower-level station is configured as a "master
station".
–
Station
With the classic network types dedicated line and dialup network, a modem needs to be
connected to the serial interface of the TIM. You select the suitable modem type using the
following parameters (serial interface only):