NIM Primitives
4-22
TIWAY 1 TI505 NIM User Manual
Symbol
Value
Definition
DDDD
17
Attached device did not respond properly
19
Resulting data element location formed by the starting
address, plus the number of data element to access, is out of
range specified by TT
1A
Communication has not been established with the attached
device
1B
Store and forward buffer is full and the store and forward
message was discarded
1C
Data element field (specified by TT) is improperly formatted
1D
Number of locations to access equals zero (NNNN = 0)
23
Number of data blocks defined in a data acquisition record
exceeds the maximum supported
80DD
Exception generated in the attached device is not
identified
TT
Optional data element type