Installation Instructions 

Models TSM-1X  

Intelligent Test Switch Module with Dual Isolators 

 

INTRODUCTION

 

The Model TSM-1X Intelligent Test Switch Module, P/N 
S54370-B7-A1, from Siemens Industry, Inc. is an 
addressable, key-activated momentary switch (T-45) 
with a tri-color LED indicator for use with intelligent 
duct detectors or other compatible intelligent devices on 
the Device Loop Circuit of Desigo 
FC2025/FC2050/FV2025/FV2050 and Cerberus PRO 
FC922/FC924/FV922/FV924 Fire Alarm Systems 
(refer to Figure 1). The key activation will cause its 
associated intelligent duct detectors or other smoke 
detectors and compatible devices to go into alarm. 
This alarm condition will cause all logic associated 
with the duct detector to activate. The 3-color LED of 
the module will show the status of its associated 
intelligent duct detector. The TSM-1X is mounted on a 
switch plate and can be installed in a 3½ inch deep 
single gang box.  

 

The TSM-1X module supports two operation modes: 
polarity insensitive mode and isolator mode. The 
module can be wired for either mode (refer to Figures 
3 to 4). During the isolator mode, the built-in dual 
isolators will work at both sides of the module to 
isolate the line short in front or behind the module. 

Observe precautions for handling 
Electrostatic Sensitive Devices.
 

 

PROGRAMMING 

1.  Refer to Figure 2 to locate the programming 

holes on back of the TSM-1X.  

2.  To connect the TSM-1X to the DPU 

Programmer/Tester, insert the plug from the DPU 
cable provided with the Programmer/ Tester into 
the programming holes. 

3.  To prevent potential damage to the DPU, DO 

NOT connect a TSM-1X to the DPU until all 
conductors of the same polarity are removed from 
the device line of the TSM-1X. 

4.  Follow the steps in the DPU Manual, P/N 315-

033260, to program the TSM-1X to the desired 
address. Record the device address on the label 
located on the side of the TSM-1X module.  

5.

 

Add a logic function in the system configuration 
tool, Document ID A6V10315023, with the 
intelligent duct detector or other compatible 
intelligent devices that will be tested. The TSM-1X 
can now be installed and wired to the system.

 

 

A6V101055486_en--_a 

  

 

  

 

 Figure 1

 

 TSM-1X Intelligent Test Switch Module 

 
 
 

 

 

 

Figure 2 
Connecting to the DPU Plug 

 

 
 
 

 

 

 

 

 

 

Siemens Industry, Inc. 

Building Technologies Division 

Florham Park, New Jersey  

Programming holes

are polarity insensitive -

Plug can be inserted

in any direction.

firealarmresources.com

Summary of Contents for TSM-1X

Page 1: ...ator mode the built in dual isolators will work at both sides of the module to isolate the line short in front or behind the module Observe precautions for handling Electrostatic Sensitive Devices PROGRAMMING 1 Refer to Figure 2 to locate the programming holes on back of the TSM 1X 2 To connect the TSM 1X to the DPU Programmer Tester insert the plug from the DPU cable provided with the Programmer ...

Page 2: ...rovided Refer to Figure 5 NOTES 1 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated between two modules in isolator mode in a Class A Style 6 wiring 2 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode ...

Page 3: ...x average current RMS 500µA CONTROL AND INDICATORS The LED of TSM 1X will mimic the LED of the associated duct detectors or other compatible intelligent devices The logic function is setup in the system configuration tool The LED flashing rate is shown in the chart below Flash Color Condition Flash Intervals Seconds Green Normal supervisory operation 10 Amber Device is in trouble 4 Red Alarm 1 No ...

Page 4: ...atest security threats patches and other mitigation measures http www siemens com cert en cert security advisories htm FCC Statement WARNING Installation and usage of equipment not in accordance with instructions manual may result in Radiation of radio frequency energy Interference to radio communications Install and use equipment in accordance with instructions manual Read the following informati...

Reviews: