CAUTION:

 

The  TSM-1X  Test Switch  Module  does  not  perform  all  of  the  required  smoke  detector  tests  as 
specified  in  NFPA  Standard  72.  Please  refer  to  the  instructions  that  accompany  the  smoke 
detector for the complete test requirements.

 

 

 

ELECTRICAL RATINGS 

Operating voltage  

13 -32 Vdc 

Max average current (RMS)  

500µA 

 

CONTROL AND INDICATORS 

The LED of TSM-1X will mimic the LED of the associated duct detectors or other compatible 
intelligent devices. The logic function is setup in the system configuration tool. 

The LED flashing rate is shown in the chart below: 

Flash Color 

Condition 

Flash Intervals  

(Seconds) 

Green 

Normal supervisory operation 

10  

Amber 

Device is in trouble 

4  

Red 

Alarm 

1  

No Flashes 

No power or need to be replaced 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A6V101055486_en--_a 

 

 

 

 

 

firealarmresources.com

Summary of Contents for TSM-1X

Page 1: ...ator mode the built in dual isolators will work at both sides of the module to isolate the line short in front or behind the module Observe precautions for handling Electrostatic Sensitive Devices PROGRAMMING 1 Refer to Figure 2 to locate the programming holes on back of the TSM 1X 2 To connect the TSM 1X to the DPU Programmer Tester insert the plug from the DPU cable provided with the Programmer ...

Page 2: ...rovided Refer to Figure 5 NOTES 1 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated between two modules in isolator mode in a Class A Style 6 wiring 2 In the device line up to 30 of any compatible devices in polarity insensitive mode with 20 ohms max line resistance can be isolated behind one module in isolator mode ...

Page 3: ...x average current RMS 500µA CONTROL AND INDICATORS The LED of TSM 1X will mimic the LED of the associated duct detectors or other compatible intelligent devices The logic function is setup in the system configuration tool The LED flashing rate is shown in the chart below Flash Color Condition Flash Intervals Seconds Green Normal supervisory operation 10 Amber Device is in trouble 4 Red Alarm 1 No ...

Page 4: ...atest security threats patches and other mitigation measures http www siemens com cert en cert security advisories htm FCC Statement WARNING Installation and usage of equipment not in accordance with instructions manual may result in Radiation of radio frequency energy Interference to radio communications Install and use equipment in accordance with instructions manual Read the following informati...

Reviews: