INTEGRAL RSA

K21-04.10

1/8

Application controllers

en  -  06.2001

Siemens Building Technologies

Landis & Staefa Division

NRK16/A (with NSA)

NRK16-B/A (with NSA)

Types

NRK16/A

Application controller with ten universal inputs

1)

 and

two analogue, two digital and two combined outputs

NRK16-B/A

Like NRK16/A, but with panel for simple local operation

NSA

Application modules, varying according to country or region,

for plugging into base units

NRK16-T../A

NRK16/A + NITEL integrated communications module for a maximum

of three additional devices (see manual NT21)

NRK14-T../A

Like NRK16-T../A, but without analogue outputs (see

manual NT21)

NRK16-WEB/A

NRK16/A + integrated NIWEB communications module for operation

of up to 15 additional devices via the Internet (K1-07.62)

Technical data

Supply voltage

Extra low voltage (SELV-E)

Nominal voltage

AC 24 V, 50/60 Hz

–  Max. tolerance

+15 / –10 %

Power consumption

– Without output peripherals

3 VA

– With output peripherals

Max. 12 VA

Fuse

Thermal element (PTC)

Supply voltage for peripheral devices

and remote operator terminal

Output voltage

DC15V ±10%,  electrically  isolated  from  AC24V

Output current

Max. 150 mA

Signal inputs 

2)

Universal inputs 

3)

– Number10

1)

–  Use

Can be structured as T1, Ni1000, DC 0...10 V,

digital volt-free, or for connection of NMID

– Input impedance

Ri (pull-up resistor) = 10 k

W

 to DC +15 V or

100 k

W

 to GND (change-over, see p. 6)

Remote control input

– Use

Can  be  structured  as  T1,  Ni1000,  DC  0  ...  10  V,

min. 1.5 sink, digital volt-free contacts, or NMID

– Input impedance

Ri (pull-up resistor) = 10 k

W

 to DC +15 V

Signal outputs 

2)

Digital outputs

– Number2

– Signal

DC 0 / 24 V, –20 / +15 %

– Source current

Max. 50 mA

Analogue outputs

– Number2

– Range

DC 0 ... 10 V

– Source/sink current

Max. 2 mA

Technical data continued on page 2

Electrical protection

The power supply is overload-protected

with a PTC thermal element.
All DC voltages are electrically isolated

from the AC 24 V input.
All the inputs are protected against over-

voltage (max. AC/DC 45 V). Low-pass fil-

ters prevent fluctuations in measurement.
All outputs are sustained short-circuit

proof.
High frequency interference is suppres-

sed by means of filters, or in the case of

capacitive interference, discharged via

the (earthed) housing or the TE terminal

(functional earth).

Important:
For direction connection of AC 24 V

3-wire peripheral devices, "GND"

and "NS" (

^

) must be connected.

NRK16/A, NRK16-B/A,

(NRK16-T../A, NRK14-T../A,

NRK16-WEB/A)

Control and interlock devices

Application controllers with

pre-programmed system-specific

application modules.
The controllers may be used
– as stand-alone control and

interlock devices

– for remote process control within

a management system

Especially suitable for use in small

heating, ventilation and air

conditioning systems.

1)

The NMID multiplexer enables four digital

inputs to be connected to a universal

output. (see K21-06.55). The function is

integrated by use of a structure macro.

2)

When connecting peripheral devices

with special input or output signals

(e.g. Pt100, phase cut or 3-position sig-

nals), the NTIO (NTIOS) single module

carrier or an NATU adapter can be

used. (See K21-06.50 and K21-06.52).

3)

The T1/Ni1000 supply voltage can be

disabled at the inputs (see page 5). DIP

switches are provided to switch the

inputs from T1 to Ni1000 and vice versa.

Summary of Contents for Types NRK 16-T../A

Page 1: ...igitaloutputs Number 2 Signal DC 0 24 V 20 15 Source current Max 50 mA Analogueoutputs Number 2 Range DC 0 10 V Source sink current Max 2 mA Technical data continued on page 2 Electrical protection The power supply is overload protected with a PTC thermal element All DC voltages are electrically isolated from the AC 24 V input All the inputs are protected against over voltage max AC DC 45 V Low pa...

Page 2: ... baud Max cable length RS bus 2400 m NRK16 A connection to RS bus From service socket via 10 core ribbon cable to NARB A adapter Service terminal NBRN operator terminal plugs directly into service socket Weight excluding packaging NRK16 A 1 15 kg NRK16 B A 1 25 kg NSA application module 0 06 kg Dimensions W x H x D NRK16 A 162 x 252 x 52 mm NSA application module 24 x 59 x 49 mm Mounting Snap moun...

Page 3: ...M also holds the NBRN modifiable setpoints parameters and time programmes but not the setpoints from the local operator panel of the NRK16 B A Construction Essentially the base unit consists of a metal housing and printed circuit board The housing comprises a base and a cover and accommodates the PCB and two part plug in connection terminals These terminals are accessible at the top and bottom of ...

Page 4: ...oving the mo dule the base unit must be discon nected from the power supply Do not touch the contact pins in the base unit 252 52 162 59 49 24 15 203 92 00158 Opening the controller 1 Ensure that the necessary EMC precautions have been taken 2 Undo the four cross head screws between the terminal blocks 3 Carefully lift off the cover For the NRK16 B A Press the four white plastic clips together wit...

Page 5: ... Ni1000 Sensors with T1 or Ni1000 measuring elements Various ZM100 A Teminal housing for DC 0 10 V valves CA2N4591 NTIO Single terminal module carrier K21 06 50 NATU Adapter for special signals K21 06 52 NMID Multiplexer toincreasethenumberofdigitalinputs K21 06 55 Room operating units see page 7 1 2 A UI01 1 2 B UI02 1 2 C UI03 1 2 D UI04 1 2 E UI05 1 2 F UI06 1 2 G UI07 1 2 H UI08 1 2 I UI09 1 2...

Page 6: ...nted circuit board and cannot be adjusted withoutopeningthecontrollerhousing When delivered from the factory the jumper settings are such that the sensor supply voltage is enabled To disable the supply each jumper must be movedonepositiontotheleft Settings for switch S182 T1 Ni1000 1 2 Sensor Inputs OFF T1 UI01 to UI08 OFF T1 UI09 to UI16 ON Ni1000 1 UI01 to UI08 ON Ni1000 1 UI09 to UI16 The facto...

Page 7: ...ofroomtemperature CA2N1655 See the relevant documentation for maximum cable lengths OperationviaRSbus Since the controller is compatible with the RS bus it can be operated remotely from any of the following devices NBE remote operator terminal see K21 05 18 NBRN operator terminal see K21 05 10 and 12 From a PC running the INTEGRAL DIALOG service software connected via the NITEL communications modu...

Page 8: ...ED display panel by use of the appropri ate selector key The setpoints can be modified with the and keys these also operate as repeating keys when continuously depressed Each of the four values is associated with one of the red channel LEDs With some applications the setpoints can have upper and lower limits adjustable from an operator terminal LED function test Depressing the two lower selector k...

Reviews: