background image

GAMMA 

instabus

 

Technical Specification 

March 2010 

Colour touch panel UP 588/13 

5WG1 588-2AB13 

Colour touch panel UP 588/23 

5WG1 588-2AB23 

 

 
Accessories: 
Design frame aluminium  

5WG1 588-8AB12 

Design frame stainless steel design 

5WG1 588-8AB13 

Design frame glass black 

5WG1 588-8AB14 

Design frame glass white 

5WG1 588-8AB15 

 

flush-type box 

5WG1 588-8EB01 

 

Technical Manual 

UP 588, 6 pages 

Siemens AG

 

 

 

Industry Sector, Building Technologies 

Update: http://www.siemens.com/gamma 

© Siemens AG 2010 

Low Voltage Distribution

 

 

Subject to change without further notice 

PO Box 10 09 53, D-93009 Regensburg 

2.3.1.7/4

 

 

C3

C3.1

C3.3 C3.2

5 mm

C3

C3.4

C3

C3.4

"A"

C4.1

"B"

6....7mm

 

C4.2

 

C4

 

 

 

 

The bus cable is connected via a standard bus terminal 

D

which is plugged into the corresponding terminal slot on 
the right side of the housing. On the left, beside the 
plug-in slot for the bus terminal are the programming 
button 

C

 and the programming LED 

B

. The connection 

terminal for the 230 V power supply or, in the 24 V 
version for 24 V  supply are on the left side 

A

 of the 

device. The terminal must be removed to connect the 
power supply. 
It is essential to obey the connection sequence marked 
on the housing! 

 
 
Mounting and wiring 

 
General description 
The device 

2

 may only be mounted in the flush-type box 

1

, to be ordered as an accessory. When the cable is 

brought into the flush-type box, take care that the bus 
cable is fed in through the bottom left hand recess and 
the power supply cable is fed in through the right hand 
recess. The bus and power supply cables must not be fed 
into the flush-type box through the same recess. Inside 
the box, the cable is to be routed so that there is a 
guaranteed separation of at least 10 mm between bus 
and power supply cables. 
 
Connecting the bus cable (figure 4 "A") 

 

The bus terminal (C3) is suitable for solid conductors 

with a diameter of 0.6 ... 0.8 mm. 

 

Strip off approx. 3 cm of the bus cable insulation 

 

Strip the insulation from the conductors (C3.4) to a 

distance of approx. 5 mm and plug it into the 
terminal (C3) (red = +, grey = -). 

 
Clipping on bus terminal (figure 4) 

 

Plug the bus terminal into the guide slot and press it 

(C3) downwards to the end stop 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 4:

 Connections

 

 
Connecting the power supply (Figure 4 "B") 

 

Strip the insulation from the conductor (C4.1) to a 

distance of 6...7 mm, plug it into the power supply 
connection terminals (C4) and tighten the screws 
(C4.2).  

 
Terminal assignment: 
 
 230V 

24V 

  1   

 

    Earth  

In1:     ± DC: AC 

  2  N 

 

  Neutral conductor  

not connected 

  3  L    Phase 

In2:     ± DC: AC 

 
After connecting the bus terminal and the power supply 
to the conductors, the terminals are plugged into the 
corresponding outlets on the touch panel. The power 
supply must only be switched on when the plug is 
engaged firmly in the device. After switching on the bus 
voltage and the power supply, the programming button 
can be pressed and the physical device address 
programmed. The LED must go out after programming 
the physical address.  
The device is then screwed into the flush-type box with 
the four screws 

3

 enclosed (see figure 3). 

The protective film applied to the display surface can 
now be removed. Do not use any sharp items or tools to 
do this. 
After the screwing the display modul and the removal of 
the protective film, the design frame 

4

 can be plugged 

Summary of Contents for UP 588/13

Page 1: ...efore function as the master timer in a KNX system Via the system settings one of four different design templates can be selected for the display and operator interface The following accessories are needed for the colour touch panel Design frame aluminium 5WG1 588 8AB12 Design frame stainless steel design 5WG1 588 8AB13 Design frame glass black 5WG1 588 8AB14 Design frame glass white 5WG1 588 8AB1...

Page 2: ...power supply For planning and construction of electric installations the relevant guidelines regulations and standards of the respective country are to be considered Technical specifications Power supplies Bus voltage via the bus line External power supply for Colour Touch panel UP 588 13 230 V AC 10 50 60 Hz Colour Touch panel UP 588 23 18 36 V DC 400 mA base isolated comp 230 V 14 28 V AC 400 mA...

Page 3: ...ory III Bus safety extra low voltage SELV 24V DC Device complies with EN50090 2 2 EMC requirements Complies with EN 61000 6 3 EN 61000 6 2 and EN 50090 2 2 Ambient conditions Climatic withstand capability EN 50090 2 2 Ambient operating conditions 0 C to 45 C Storage temperature 25 C to 70 C Relative humidity non condensing 5 to 93 Markings KNX EIB EC mark In accordance with the EMC guideline resid...

Page 4: ... power supply cables must not be fed into the flush type box through the same recess Inside the box the cable is to be routed so that there is a guaranteed separation of at least 10 mm between bus and power supply cables Connecting the bus cable figure 4 A The bus terminal C3 is suitable for solid conductors with a diameter of 0 6 0 8 mm Strip off approx 3 cm of the bus cable insulation Strip the ...

Page 5: ...val can be made easier by lifting the power supply connection terminal C4 slightly with a flat bladed screwdriver To do this push the blade of the screwdriver into the centre of the terminal detente between the power supply connection terminal C4 and the base of the slot Removing the bus terminal figure 4 A The bus terminal C3 is in the left slot It consists of two parts C3 2 and C3 3 each with fo...

Page 6: ...the touch panel It has a length of 1 m and have a transfer rate of 480 MBit sec After completing the transfer remove the cable and mount the design frame as described above Care instructions The display s design frame and plastic surface can be cleaned with off the shelf solvent free cleaning agents The display surface itself should be cleaned with a soft damp cloth e g spectacles cloth and if nec...

Reviews: