UTMC OTU/MOVA Handbook
667/HB/31601/000
Page 88
Issue 5
Typical MOVA Main Menu Screen
SIEMENS MOVA COMMISSIONING SCREEN:J12345
Detectors: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Confirms:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
CRB
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Force Bits:
HI/TO 1 2 3 4 5 6 7 8 9 10
MOVA enabled. . 1 Warmup. . . . . 6 Multi stage . . 0 On control. . . 1
Demanded stage . . . 1 Watchdog . . . 9 Error count . . . 0
SIEMENS MOVA MAIN MENU
DS - DataSet menu VM - View MOVA Messages DF - Display Flows
for operations: DE - Display Error log CF - Clear Flows
Display, Load CE - Clear Error log LF - Look at/set Flags
Download, Upload DA - Display Assessment log CT - Check/set Time
CA - Clear Assessment log FI - FInish
Press a Key:
--- Press a key listed above or Press <Space> for Main Menu ---
While the MOVA Main Menu is being displayed, enter the two-letter menu option
required and press ‘Return’. When the required option completes, the main screen will
automatically re-appear.
7.3.10 The Error Log (DE and CE)
7.3.10 Check that the Error Log contains no unexpected entries and then
clear the error log.
To display the error log, enter ‘DE’ from the main menu,
This displays time stamped reports of any warnings or errors detected by the MOVA
unit. This log may help diagnose the reason why the MOVA unit has gone off control for
example.
At the end of the log, the MOVA unit will display some debug information that can
normally be ignored:
CRASH(1-4)= 0 0 0 0
TERM= 0 RCV(2)= 0 ABO= 0
To clear the error log, enter ‘CE’ from the main menu.
It is recommended that the error log be cleared after each site visit if all entries can be
explained and the unit is functioning normally. Then the engineer making the next visit
to site will only see faults that have occurred since the last visit.