Building Technologies 

Network Node WTT16…, WTX16… 

CE1N2874en 

HVAC Products 

 

14.07.2005 

as a confirmation. The result would be an erroneous display when showing the remain-
ing capacity. 
 
First, remove the discharged main battery and insert the new one. Press the blue 
DISPLAY button once to start the life expectancy calculation for the new main battery. 
The backup battery MUST NOT be removed simultaneously. A fatal loss of data would 
happen. 
 
After storing the main battery for longer periods, especially at temperatures higher than 
30 °C, the battery might passivate. Under these circumstances it will not be able to 
deliver sufficient energy to the network node. If the network node detects a passivated 
battery a de-passivation cycle is triggered. This is indicated by a flashing front LED. 
The procedure might take a few minutes. After de-passivation the network node will 
start up in IdLE   mode. Low temperatures at the battery may cause a similar behavior 
in other modes too. 
 
The main battery used by the WTT16… requires careful treatment: 

  Do not short-circuit or damage the battery 

  Do not expose the battery to excessive heat 

  Return exhausted batteries to the supplier 

  Read the enclosed safety instructions carefully 

M-Bus connection 

Any network node can be connected to the M-Bus temporarily (service connector) or 
continuously (screw terminal for the fixed M-bus connection). A plug for the screw ter-
minal is included with every network node. 

RESET

MODE

Screw terminal for the fixed

M-Bus connection

max. 5 unit loads

 M-Bus  service connection

 

Technical data 

 conformity to EMC directives 

 

Safety class  

IP32 

Safety class  

Electromagnetic compatibility 

immunity:  EN 55 024/EN 301 489 
emissions:  EN 55 022/EN 300 220-1 

Operating voltage WTT16… 

DC 3.6 V 

Lifetime of main battery 

> 5 years 

Operating voltage WTX16… 

AC 100…240 V, 50/60Hz 

Rated frequency  

868.3 MHz  

Transmitter power  

< 14 dBm  

Frequency of transmission 

<1% 

Perm. ambient temperature  
 

Transport and storage 

 Operation 

 

20…+60 °C (< 30°C recommended) 

0…55 °C 

Weight 

0.3 kg  

 

Battery replacement 

De-passivation 

Safety notes on  
lithium batteries 

Summary of Contents for WTT16 Series

Page 1: ...nent of the Siemeca system It has been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building Communication between several network nodes is via radio also so that no wiring is required All meas ured values acquired by the consumption meters are continuously exchanged within the network which means ...

Page 2: ... system must not be ex ceeded The network nodes with gateway and integrated M Bus master WTX16 GSM and WTX16 IP are able to read M Bus meters according to EN1434 3 Technical design The network node consists of the following subassemblies transceiver for Siemeca network memory for 500 meters M Bus Slave RS232 optional backup battery power supply mains supply WTX16 battery WTT16 Receiver and transmi...

Page 3: ...ton for switching the display blue 8 Reset button recessed 9 Display 10 Connector not for the user 11 Firmware memory covered up The wall mounted section of the network nodes WTT16 contains only the main battery The wall mounted section of the network nodes WTX16 and WTX16 232 contains the power pack and possibly an additional RS232 interface GND n c RTS CTS Rx Tx 4 2 7 3 5 6 1 1 Mains connection ...

Page 4: ...ing de vices are received stored and further handled by the network Extended standard mode1 M The receiver is always active to ensure fast communication This mode is automatically activated in the case of mains powered opera tion WTX16 It can also be started manually with the ACT26 service tool Installation mo de2 In installation mode the radio network will be configured automatically Metering dev...

Page 5: ...onal interface s CAUTION connect the mains cable to the power supply unit only 1 2 3 1 Mains connection L and N 2 Preinstalled mains cable no flexible power cable 3 Extra insulation shrink sleeve Connect the AC 230 V power supply line to the power pack of the WTX16 in the following order Remove the upper housing section of the WTX16 from the base For that purpose remove the 2 cable connections pow...

Page 6: ...aintained Staff dealing with the product must be familiar with all potential hazards and mainte nance measures in accordance with the instructions given in this document Non observance of these warning notes can lead to personal injury or damage to property Ensure that the local regulations for radio transmission installations and electrical instal lations are complied with Pursuant to the Verordn...

Page 7: ...similar behavior in other modes too The main battery used by the WTT16 requires careful treatment Do not short circuit or damage the battery Do not expose the battery to excessive heat Return exhausted batteries to the supplier Read the enclosed safety instructions carefully M Bus connection Any network node can be connected to the M Bus temporarily service connector or continuously screw terminal...

Page 8: ...ions in mm WTX16 WTT16 The information provided in this Data Sheet only gives general descriptions and general technical features which in the case of specific applications may not necessarily apply or which may change due to further development of the product Technical features are binding only when expressly agreed upon at the time a contract is concluded 2002 Siemens Building Technologies AG Su...

Reviews: