Operating manual     

 

TR 1200 

Pt 100 thermostat with 12 sensor ports and Interface RS485 
 
 
 
 

 

 

 

MINIPAN

®

 Digital meter, Temperature and Network Monitoring 

Special purpose units on cus www.ziehl.de

 

 

Summary of Contents for ZIEHL TR 1200

Page 1: ...ustrie elektronik GmbH Co KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de Operating manual TR 1200 Pt 100 thermostat with 12 sensor ports and Interface RS485 MINIPAN Digital meter Temperature and Network Monitoring Special purpose units on cus www ziehl de ...

Page 2: ... diagram 7 8 Commissioning 7 8 1 Operating diagram 7 8 2 Parameter description 8 8 3 Display mode 8 8 4 Menu mode 8 8 5 Configuration mode 9 8 6 2 wire line resistance compensation 9 8 7 Sensor configuration 9 8 8 Relay configuration 10 8 9 RS485 Interface configuration 10 8 10 Simulation 11 8 11 Code lock 11 8 12 Possible indications in display 12 9 Factory settings and software version 13 10 Mai...

Page 3: ...0 measure the temperature of up to 12 Pt 100 thermometers With the RS485 Interface measured temperature values can be issued i e for remote control or further evaluation One error relay monitors sensor failures und signals general malfunctions 2 Overview of functions 3 digit temperature display 12 inputs for temperature sensors 1 12 sensors can be connected Pt 100 thermostats with 2 or 3 wire conn...

Page 4: ...4 Hindmost decimal point red OFF Display mode Illuminated Menu mode flashes Parameter mode 5 LED error red OFF normal operation Illuminated with 8Er1 Er1 Er1 Er18 8E E E Er2 r2 r2 r28 8Er8 Er8 Er8 Er88 or 8Er Er Er Er9 9 9 98 Sensor error malfunction invalid parameter 6 Button Up Down display mode normal operation Press briefly Change into the menu mode see Operating instructions Point 8 4 Press f...

Page 5: ...y and operate as directed Only let persons work with the equipment who are familiar with installation start and use and who have appropriate qualification corresponding to their function They must observe the contents of the instructions manual the information which are written on the equipment and the relevant security instructions for the setting up and the use of electrical units The equipments...

Page 6: ...ts and the RS485 interface are applied to the same electrical potential but are galvanically isolated 2kV for the auxiliary voltage Take this into consideration during configuration RS485 connection Use RS485 Interface only with shielded wires Large cable lengths may shift the potential ground and the transmission can be disturbed Corrective measures can be galvanic separation or an additional gro...

Page 7: ... 49 791 504 0 Fax 56 e mail info ziehl de 7 Connection diagram 8 Commissioning 8 1 Control chart unit Up Down together resets values to Zero Code Reset press 2 s Set when switching on supply voltage Pin 504 Error Code EE under range EEE over range Er1 short circuit sensor Er2 interruption sensor Er8 Internal device error Er9 invalide parameter alternating Display ...

Page 8: ...ud rate 8bdr bdr bdr bdr8 Set the baud rate 8 48 48 48 488 4800 8 96 96 96 968 9600 8192 192 192 1928 19200 Parity 8par par par par8 Set the parity bit 8eve eve eve eve8 even 8odd odd odd odd8 odd 8 no no no no8 none 8 3 Display mode last decimal point off In the display mode the TR 1200 is in its normal state here the temperature of the selected sensor is displayed In addition the error codes e g...

Page 9: ...f you keep the Up or Down key pressed while setting a value the speed of the change in the display is accelerated 8 6 2 wire technique line resistance compensation Connect the sensor at terminals xT1 and xT3 xT2 has to be open To compensate the line resistance short circuit the wires nearby the sensor and measure the line resistance We recommend using 2 or bettering 3 wires for each sensor With 2 ...

Page 10: ... prt prt8 8485 485 485 4858 Protocol 485 flash alternately Set the desired protocol using the Up and Down keys Press the Set key Display 8adr adr adr adr8 8 0 0 0 08 Device address Value flash alternately Set the desired device address using the Up and Down keys Press the Set key Display 8bdr bdr bdr bdr8 8 96 96 96 968 Baud rate Value flash alternately Set the desired baud rate using the Up and D...

Page 11: ...eys Press the Set key exits the simulation mode Display 8si si si si 8 Simulation 8 11 Code lock Here the set parameters can be protected by activating a code lock The device acknowledges an incorrect entry with 8err err err err8 flashes three times Adjustment process Select the menu item with the Up Down key until Display 8Cod Cod Cod Cod 8 Code lock Press the Set key Display 8Pin Pin Pin Pin8 8 ...

Page 12: ...tem sensor configuration 8S 1 S 1 S 1 S 18 8S12 S12 S12 S128 Sensors 1 12 83 3 3 3 L L L L8 3 conductor connection 8 nc nc nc nc8 No sensor connected 8rel rel rel rel8 Relay function 8bus bus bus bus 8 Menu item for configuring the RS485 interface 8Prt Prt Prt Prt 8 Protocol RS485 interface 8485 485 485 4858 RS485 protocol 8Mod Mod Mod Mod8 Modbus protocol 8adr adr adr adr8 Device address RS485 in...

Page 13: ...S 9 S 9 S 98 Sensor 9 8 nc nc nc nc8 8S10 S10 S10 S108 Sensor 10 8 nc nc nc nc8 8S11 S11 S11 S118 Sensor 11 8 nc nc nc nc8 Sen Sen Sen Sen 8S12 S12 S12 S128 Sensor 12 8 nc nc nc nc8 rel rel rel rel 8rel rel rel rel8 Relay function 8 r r r r8 8prt prt prt prt8 Protocol 8485 485 485 4858 8adr adr adr adr8 Unit address 8 0 0 0 08 8bdr bdr bdr bdr8 Baud rate 8 96 96 96 968 Bus Bus Bus Bus 8par par par...

Page 14: ...ntinues to appear the unit must be returned to the factory for repair 8Er9 Er9 Er9 Er98 Invalid parameter Press button SET for 10 s when switching on supply voltage for factory settings Wrong temperature values Sensors with 3 wire technique interchanged Check sensors with 3 wire technique Terminals of sensor 1 6 are not compatible to terminals sensor 7 12 Parameter configuration not allowed Code l...

Page 15: ... depending on number of sensors Measuring time line resistance 0 25 30s each cycle of a sensor Measuring range 199 850 C Resolution 1 C Sensor connection 12 x Pt 100 according EN 60751 temperature range C Short circuit Ohm Interruption Ohm Pt 100 RL Ohm Sensor min max max Pt 100 199 860 15 400 500 Measuring accuracy 0 5 of measuring value 1 K Sensor current 0 8 mA Temperature drift 0 04 C K RS485 ...

Page 16: ...ight width 55 mm 8 TE Wire connection single wire each 1 x 1 5 mm2 Stranded wire with insulated ferrules each 1 x 1 0 mm2 Torque of screw 0 5 Nm 3 6 lb in Protection class housing terminals IP 30 IP 20 Fitting position any Installation Snap mounting on mounting rail 35 mm according to EN 60 715 or with screws M 4 additional bar in scope of delivery Weight app 350 g Subject to technical changes 13 ...

Page 17: ...Protocols The TR 1200 optionally supports the Modbus or the ZIEHL RS485 protocol Device data and measurements can be read out with both protocols in addition the TR 1200 can be configured using the Modbus protocol The protocol is selected in the menu item 8bus 8 see 8 9 Configuring RS485 interface 14 1 Modbus protocol You can find documentation on the Modbus protocol in the Internet at www ziehl c...

Page 18: ...bytes 3 Byte Carriage Return CR 0x0D 1 Byte Line Feed LF 0x0A 1 Byte 10 Byte TR 1200 sends the requested data TR sends start type of unit address of unit mode data BCC CR LF Start of message s ASCII or S ASCII or STX 0x02 1 Byte same as request Type of unit TR600 ASCII or TR120 ASCII 5 Byte Address of unit 0 99 ASCII 2 Byte Data mode 0 9 ASCII 1 Byte Value sensor 1 7 199 850 ASCII 4 Byte Value sen...

Page 19: ...115 EXOR 0 48 EXOR 1 49 EXOR r 114 EXOR 0 48 048 The values in brackets correspond with the ASCII code of the sign Answer sTR600 01 0 154 055 268 999 980 999 1 0 0 1 0 0 1 02 119 r n Data mode Address of unit Type of unit Start of message Temp Sensors Alarm 1 7 Internal error Block sum End of message Para meter Answer of TR unit Address of unit Data mode Request Transmission Start of message Type ...

Page 20: ... adr8 to 0 The TR 1200 transmits the data from Sensors 1 6 cyclically every 3s under device address 0 6 RTD Semiduplex 1x TR 1200 works like 1x TR 600 Connect Sensors 1 6 Configure Sensors 1 6 in menu item 8SEN SEN SEN SEN 8 depending on the connection configure sensors that are not connected as nc Configure Sensors 7 12 in menu item 8SEN SEN SEN SEN 8 as nc Set device address in menu item 8bus bu...