8
Figure 3: Adjustable Mount Brackets
Using adjustable mount brackets, attach PDU to rack as shown
Network Overview
This product comes preconfigured with a default IP address set. Simply connect to the PDU and
access the web page with your browser.
Default IP Address
7M, 7N, 7S and 7W units have a default IP address for initial setup and access to the unit if the
assigned address is lost or forgotten. Once an IP address is assigned to a unit, the default IP
address is no longer active. To restore the default IP address, press and hold the reset button
located below the network connector for 20 seconds while the unit is powered up. The Idle and
Activity lights next to the network connector will both light up when the IP address has been
reset. The reset button is accessed through the white, circular hole located below the Ethernet
jack.
Note:
Pressing the reset button under the network connector will restore the default IP address and will
also clear all password settings.