MapIT G2 Hardware Installation Training Manual
Confidential – June 2014
10
DCP is almost exactly the same as the MCP with two key exceptions
– 1) it does not
have Ethernet ports and 2) it has an S110 and RJ45 for connection to the MCP.
Distribution Control Panel Dimensions
Component
Width
Height
Depth
DCP
483 mm
19 inches
45 mm
1.75 in
170 mm
7.0 in
Supplied Components
-
DCP
-
24 S310 stuffer caps
-
Sensor pen
-
Rear cable manager & cable ties
-
DC power supply
-
Installation instructions
The Front of the Distribution Control Panel (DCP)
1. 24 RJ45 I/O Control Bus
– For connections to SPP/SFEs. Use either these RJ45s
or the S310s (on rear of panel). DO NOT
connect both the RJ45 and S310 of a
single port simultaneously. If the RJ45s are used, Siemon recommends putting the
supplied S310 stuffer caps on the S310 ports on the rear of the panel. If S310s are
used, use the Siemon RJ45 port blockers (p/n LL-05, sold separately). Always use
T568A wiring scheme for all cables connected to these ports.
2. LCD
– 4 Line LCD used to view the DCP menu
3. Alphanumeric Keypad
– Use to input information to the Distribution Panel
4. Scroll and Enter Buttons
–
Used to navigate the DCP menus and input data
5. Sensor Pen Port
–
Insert supplied probe pen here. Pen can be used for system
diagnostics, circuit trace, mapping and more