Siemon PowerMax™ User Manual v1.3.0
56
5 Technology Parameters
No
Performance parameter
Technical parameter
1
Input
Rated input voltage
110/220VAC 50/60HZ;
380V~ 50/60 Hz;
Rated input plug
IEC60309 standard
Cable specification
16A:3×2.5mm² 32A:3×6.0mm²;
3×16A:5×2.5mm² 3×32A:5×6.0mm²
Cable length
2.5M
Max. load current
16A, 32A
3×16A, 3×32A
Overload protector
1P circuit breaker
3P circuit breaker
2
Output
Socket standard
Standard IEC320 C13
、
C19
Socket quantity
Monitored Series: 8
、
16
、
24
、
36way;
Smart Series: 8
、
16
、
24way;
Switched Series: 8
、
16
、
24way;
Managed Series: 8
、
16
、
24way;
Output voltage
110/220VAC 50/60HZ
Output current
16A
、
32A
3*16A
、
3*32A
3
Control ports
Net port
1xRJ45 port
Daisy chain port
2xRJ45 port
Software update port
1x RJ45 port
Temperature
&
humidity port
Max 2xRJ11 port
(
can add more
)
Smoke sensor port
Max 1xRJ11 port
(
optional
)
Water sensor port
Max 1xRJ11 port
(
optional
)
Door sensor port
Max 1xRJ11 port
(
optional
)
4
Display
Working state
1xLED
Power pulse
1xLED
IP
Address,
M/S
PowerMax
state,
measurement
value,
alarm state
LCD screen
(
Resolution: 128×64
)