background image

S8000II Top Dimensions

S8000II Front Dimensions

S8000II Side Dimensions

OVERALL DIMENSIONS

ACHIEVING PROPER DRAFT

Draft is the force which moves air from the appliance up

through the chimney. The amount of draft in your chimney

depends on the length of the chimney, local geography,

nearby obstructions and other factors. Too much draft may

cause excessive temperatures in the appliance. An

uncontrollable burn or a glowing red stove part or chimney

connector indicates excessive draft. Inadequate draft may

cause back puffing into the room and plugging of the

chimney. Symptoms of inadequate draft include leaking of

smoke into the room through the appliance and/or chimney

connector joints. A minimum draft of .06wc is required for

proper operation.
Your Sierra Stove must not be connected to a chimney

serving another appliance. Multiple appliances on a single

flue may cause flue gases to be drawn into the house

through an unused opening, or in the form of poor draft

and rapid creosote accumulation.
The Sierra Stove will not smoke if installed according to

manufacturer's specifications and with a listed chimney.
A scheduled plan for cleaning the chimney must be

observed.  A build-up of resins from wet or green wood can

cause a flue fire (see Maintenance Section).
Special methods are required when passing chimney

through a wall or ceiling.  See Pipe Instructions Manual

and/or local building codes.

Do Not Over-fire this Heater:

 Attempts to achieve heat

output rates that exceed heater design specifications can

result in permanent damage to the heater. 

A glowing

stove or connector pipe is hazardous!
HEARTH PROTECTION

Floor protection and/or hearth extension is required for the

Sierra Stove. All floor protection materials must be non-

combustible (i.e., metals, brick, stone, mineral fiber boards,

etc.). Floor protector must be a 1/2" minimum thickness,

non-combustible material having an equal or better

insulating value (lower "k" value) at "k"=<.84>. It must

extend from beneath the heater to the front, sides, and rear

as indicated. Any organic materials (i.e., plastics, wood.

paper products, etc.) are combustible and must not be

used. The floor protector specified may include some form

of thermal designation such as an R-value (thermal

resistance), k-factor (thermal conductivity), or C-factor

(thermal conductance). The easiest means of determining

a proposed alternate floor protector that meets the

requirements listed in this manual is to follow this

procedure:

1)

Convert specification to R-value:

i) R-value given - no conversion needed.

ii) k-factor is given with a required thickness (T)

in inches: R  1/k x t

iii) C-factor is  given: R - 1/C

2)

Determine t R-value of the proposed alternate

floor protector.

i) Use the formula in step (1) to convert values

not expressed as "R".

ii) For multiple layers, add R-values of each layer

to determine overall R-value.

3)

If the overall R-value of the system is greater

than the R-value of the specified floor

protector, the alternate is acceptable.

 Floor Protection must be provided in the following areas:

!

 Under the unit

!

 16” in front of the unit

!

  8” from the sides of the door opening

!

  Where horizontal venting us used, under the     

               connector and 2” beyond each side. 

2

Summary of Contents for S8000II

Page 1: ...ion and operation of the Sierra S8000II wood heater EMISSION CERTIFICATION STATUS The S8000II model meets the U S Environmental Protection Agency s emission limits New Source 2020 ASTM E3053 2017 and EPA Alternate Test Method ATM 125 for cordwood Under specific test conditions this heater has been shown to deliver heat at rates ranging from 16 700 to 71 300 Btu hr capable of heating approximately ...

Page 2: ... heater design specifications can result in permanent damage to the heater A glowing stove or connector pipe is hazardous HEARTH PROTECTION Floor protection and or hearth extension is required for the Sierra Stove All floor protection materials must be non combustible i e metals brick stone mineral fiber boards etc Floor protector must be a 1 2 minimum thickness non combustible material having an ...

Page 3: ...ve door and bottom air control The fire should die down once deprived of oxygen If the fire doesn t die call the fire department for assistance CAUTION In airtight stoves after closing the bottom air control volatile gases are still given off by the wood smoldering in the firebox A sudden burst of oxygen caused by opening the draft control or door while stove is smoldering will ignite the volatile...

Page 4: ...placed before using 7 The chimney should be the proper size Some fireplace chimneys are quite large and will cause poor stove performance and excessive creosote The rule of thumb is that the chimney flue should be roughly no more than three times the flue opening on the stove A 6 inch stove flue will work in an 8 inch by 12 inch fireplace flue It may be necessary to install another liner in an ove...

Page 5: ...e thickness with a ventilated thimble minimum 24 gauge in thickness having two 1 inch air channels separated from combustibles by a minimum of 6 inch of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Solid insulated listed factory build chimney length with an inside diameter 2 inch larger than the chimney connector a...

Page 6: ...tween the stove and an approved chimney but never as the chimney itself To minimize creosote formation in the chimney connector pipe place stove as close to the chimney as safety clearances will allow Never use more than two elbows Any horizontal pipe section should rise 1 4 per foot towards chimney This will allow creosote to run back into the stove Special methods are required when passing a chi...

Page 7: ... follow this procedure 1 Convent specifications to R value a R value is given no conversion is needed b K factor is given with a required thickness T in inches R 1 k T c C factor is given R 1 C 2 Determine the R value of the proposed alternate floor protector a Use the formula in step 1 to convert values not expressed as R b For multiple layers add R values of each layer to determine the overall R...

Page 8: ...tion or sections of stove connector pipe that connect the stove flue outlet to the fireplace chimney Method I is normally used and is generally the easiest to install Method II may be used in chimneys that need a new flue liner 8887 There are qualified installers in most areas that can install your stove for you Sierra recommends that you contact the National Chimney Sweep Guild for a member in yo...

Page 9: ...a 30 minimum clearance between mantel and stove top If less clearance is needed there are approved mantel shield kits available so check with your Sierra dealer 6 The Sierra Fireplace Cover Kit FPCK may be used to enhance the looks of the hearthstove installation but it is not required with the direct connection method of installation Instructions for installation are supplied with this kit THE FP...

Page 10: ...ur stove has a blower do not run the electrical cord in front or near the fire box V USING A CATALYTIC COMBUSTOR Definition and Purpose of a Catalytic Combustor Catalytic combustors for woodstoves cats are simular in principle to catalytic converters on automobiles The big difference is that the heat generated by your woodstove is put to use heating your home instead of being dumped out the tailpi...

Page 11: ... firebox heat and coal bed for the large long burn load Kindling Made from small pieces diameter and 6 12 long A hatchet works well for splitting a small piece of cord wood length wise You ll need about 4 lbs of kindling to heat up the flue and start a small draft Starting Load Made up of 2 diameter pieces 12 16 long You ll need about 6 lbs of start up fuel to build the coal bed and warm up the st...

Page 12: ...the bottom of the firebox This allows the air to get under the fire better 3a High Altitude Starting Instructions Follow all steps above l through 3 however due to the decreased density of oxygen supplied in a given volume of air at higher elevations it will be necessary to allow the stove to burn for a longer period of time with the air control rod pulled all the way out It may also be necessary ...

Page 13: ...t or oxygen present in the stove this wet and steamy smoke does not ignite and burn Instead it is drawn through the exhaust vent and into the chimney As this steam begins to cool down in the flue it condenses as droplets of moisture on the inside walls of the chimney This becomes creosote which is flammable and is the fuel which burns in a flue fire It is necessary to periodically clean these depo...

Page 14: ...re 4 If you do have a chimney fire call the fire department immediately Only then attempt to control the fire Throw soda on the logs close the draft regulators completely to shut off air to the fire Wet down your roof and adjacent areas to keep the fire from spreading 5 If you must use green wood and we urge you to avoid doinf so be sure to mix with dry logs Glass In the event that you need to cle...

Page 15: ...od Stove notify your nearest dealer or contact Sierra Products Inc at www sierraproductsinc net customer support technical service Sierra Products Inc 63 Laxalt Dr Carson City NV 89706 www sierraproductsinc net P N 140821r2 S8000II WOOD STOVE MANUAL 15 ...

Page 16: ...service center SPI may require the consumer to supply reasonable proof of the stoves purchase date This warranty is in lieu of any other express warranty Any implied warranties including but not limited to any implied warranty of merchantability or fitness for a particular purpose shall not extend beyond one year from the date of purchase The purchaser s sale and exclusive remedy shall be for the ...

Reviews: