background image

4

Figure 4

B. Solid insulated, listed factory-built chim ney

length of the sam e inside diam eter as the
chim ney connector and having 1 inch or more

of insulation w ith a minimum  9 inches air
space betw een the outer w all of the chim ney

length and com bustibles.

C. Sheet steel chim ney connector, minim um  24

gauge in thickness with a ventilated thim ble,

m inim um 24 gauge in thickness, having tw o 1
inch air channels, separated from

combustibles by a minim um of 6 inches of
glass fiber insulation.  Opening shall be

covered, and thim ble support with a sheet
steel support, minim um  24 gauge in thickness.

D. Solid insulated, listed, factory-built chim ney

length, w ith an inside diam eter 2 inch larger
than the chim ney connector, and having 1 inch

or more of insulation.  Serving as a
pass-through for a single w all sheet steel

chim ney connector of minim um 24 gauge
thickness, w ith a m inim um  2 inch air space

betw een the outer w all of the chim ney section
and com bustibles.  M inim um  length of a

chim ney section shall be 12 inches chim ney
section spaced 1inch aw ay from connector

using sheet steel support plates on both ends
of chim ney section.  Opening shall be covered,

an chim ney section supported on both sides
w ith sheet steel support securely fastened to

w all surface of m inimum  24 gauge thickness. 
Fasteners used to secure chim ney section

shall not penetrate chim ney flue liner.

E.

Proper Draft

The chimney draft greatly influences the operation. 

Too little draft can cause sm oke to puff from the
therm ostat dam per or from  the door.  To increase

draft: use a larger flue pipe, shorten connector
pipe or extend chim ney height.  Too much draft

could cause overheating.  A barom etric dam per
installed in the connector pipe close to the heater

can control excessive draft.

The flue area of the chim ney should be a minim um
area equivalent to 6" diam eter flue pipe.

If necessary, the draft can be checked by qualified

serviceman and should have a draft of .04 inches
of  w ater  colum n  m inim um   and  .07  m axim um .

Chim ney Draft

1.

Factory Build Chim neys

:  M ust be listed type

HT per UL 103.  NFPA No.211 requires factory built
chim neys to be listed and installed in accordance

w ith conditions of the listing and the
m anufacturer’s instructions.  NFPA No.211 also

requires the chim ney to extend at least 3 feet
above the highest point w here it passes through

the roof, and at least 2 feet higher than any portion
of a building w ithin 10 feet of the pipe.  (See

figures 2 & 3)

2.

Brick Chimney with Thimble

:  W hen an existing

chim ney is used be sure it is in good repair and

has a suitable chim ney flue liner.

A solid fuel heater should not be connected to the

same chimney as other heating appliances. 

Unsatisfactory perform ance can result from

variable or insufficient draft.

A connector to masonry chim ney shall extend
through the inner face or liner but not beyond, and

shall be firm ly cem ented to masonry chimney.  A
thim ble may be used to facilitate rem oval of the

chim ney connector for cleaning, in which case the
thim ble shall be perm anently cemented in place

w ith high tem perature cem ent (see figure 4).

Summary of Contents for Shenandoah R77-E

Page 1: ...fore installation Save these instructions GENERAL INFORMATION Congratulations on your purchase of the Sierra Stove W e are confident that your new stove will provide you with years of safe comfortable and efficient heating This manual describes the installation and operation of the Shenandoah R 77E wood burning heater Please read this entire manual before you install and use your new room heater F...

Page 2: ...es and extends 16 beyond the ash and loading doors and under the chimney connector 2 beyond each side 2 IF APPROVED FLOOR PROTECTION IS NOT USED Use the following calculation to determine if a proposed alternate floor protector meets the requirements listed in the appliance manual a Convert specification to R value i R value is given no conversion is needed ii K factor is given with a required thi...

Page 3: ...e keeping minimum clearances in mind It should have no more than two 90 degree elbows The horizontal connectors are required by NFPA National Fire Protection Association No 211 to have at least inch rise to the linear foot It should be easily accessible for cleaning and should not pass through walls floors or ceiling without being properly insulated for heat The connector pipe should not be instal...

Page 4: ...ion Too little draft can cause smoke to puff from the thermostat damper or from the door To increase draft use a larger flue pipe shorten connector pipe or extend chimney height Too much draft could cause overheating A barometric damper installed in the connector pipe close to the heater can control excessive draft The flue area of the chimney should be a minimum area equivalent to 6 diameter flue...

Page 5: ... place DO NOT IN ANYWAY CAUSE THE UNIT TO OVER FIRE BY OVERRIDING THE THERMOSTAT CONTROL This is an unsafe operation of the unit and could severely damage the unit as well as endanger your home For this reason this type of operation would invalidate the warranty Burning Wood To start a wood fire place crumpled newspaper on the grate and cover it with kindling wood in a criss cross pattern Then pla...

Page 6: ...above 250 degrees Fahrenheit Below 250 degrees Fahrenheit produces black liquid creosote 4 Rather than burn the heater extensively at a low setting during the mild temperatures of 50 degrees and above build a small hot fire for a short period of time Chimney inspection and cleaning The chimney and heater should be inspected for creosote buildup every two weeks during the heating season Creosote is...

Page 7: ...are stores Care should be taken to avoid damaging the flue liner Chimney cleaning service is available in most areas D Firebrick Inspection At least once a year check the condition of the firebrick lining All broken firebricks should be replaced New firebrick can be obtained from your Shenandoah dealer SERVICE TIPS To be Performed Only by Qualified Installers Re calibrating Thermostat Control Note...

Page 8: ...Side Refractory Liner 421222 Shaker Handle 422232 Outer Grate Support Plate R77 SERVICE TIPS Continued To be Performed Only by Qualified Installers 4 If neither steps 2 or 3 adjusts as desired loosen catch 2 bolts0 and position in or out as required see figure below To check for gasket seal place a folded sheet of paper between the door and frame with the door shut Pull paper to feel friction betw...

Reviews: