DISPLAY REMAINS AT ZERO OR SHOWS NO CHANGE --  If the display remains at zero or 

shows no change but the process is changing, check for DC voltage on the loop.  With 2 wire (4/20MA) 
instruments check with a DC voltmeter at the level instrument, by disconnecting the level instrument 
from its 2 wires and measuring across these 2 wires with a DC voltmeter for the presence of 24VDC.  
Check the diagnostic screen for analog input value. 
 
 
If DC voltage is present, reconnect the negative wire of the supply and insert a milliamp meter between 
the positive wires.  The loop should provide a signal between 4 and 20 MA.  If no current is present 
or & current exceeds 20MA consult the level instrument supplier. 
 
If DC voltage is not present check the user supplied power supply or if using the 700 DPCF/TPCF supply  
measure across terminals 24VDC and + and -.  If no 24VDC is present consult factory.  If 24VDC is 
present check field wiring between the 700 DPC and the field device and recheck ‘SCALE’ functions to 
ensure correct setup. 
  
 
 
 
 
 
 
 

NOTE:   This should be done by using the user provided circuit breaker or fuse, 
not by removing the power wires at the terminal block.  Serious injury or death 
can occur if contact is made with the incoming AC power. 

MAINTENANCE AND TROUBLE SHOOTING 
 
 

The Series 700 PDL is a digital solid-state device, which requires no periodic maintenance. 
 
Occasional checks of the unit should be carried out for physical and mechanical security of mounting, 
terminal blocks, and electrical wiring. 
 
 

TROUBLE SHOOTING 
 

• 

UNIT ‘LOCKS UP’ --  Recycle power to the unit by removing AC power, waiting 10 seconds and 

reconnecting power. 
 

Summary of Contents for 700 PDL Series

Page 1: ...1 VISIT OUR WEBSITE SIGMACONTROLS COM 700 SERIES PDL PROCESS DATA LOGGER INSTRUCTION MANUAL 700 SERIES PDL PROCESS DATA LOGGER 062314...

Page 2: ...cess Data Logger Showing Inputs 8 4 20 MA Digital Output 4 Form C Relays PROGRAMMING AND INITIAL SETUP 7 Input Range Selection Terminal Block Detail Initial Setup Programming Overview Key Description...

Page 3: ...ring selection Data logs all variables on user selected interval Provides USB Port for downloading logs ORDERING INFORMATION Wall Mount Nema 4X Enclosure Sigma 700 Series PDL SPECIFICATIONS ANALOG INP...

Page 4: ...e via menu prompts and user keys The preconfigured screens and pull down sub menus with English prompts assures rapid setup and commissioning 1 YEAR WARRANTY 4 M Byte data logging with USB Port MODBUS...

Page 5: ...all local state and national codes that apply Do not exceed the rated current of the D C power supply 100MA or the form C relay outputs 5A 240VAC resistive WARNING Hazardous voltages are present withi...

Page 6: ...6...

Page 7: ...have appeared the unit will show the MAIN SCREEN which scrolls as shown below NOTE To pause the screen scroll press the buttons PROGRAMMING SCREENS From the Main Menu Press the button to access the P...

Page 8: ...bers will change faster with the key held down Move to Screen 2 Press to advance to channel 2 settings Continue with setting channels 2 8 in the same way as described And return to the Main Screen ADV...

Page 9: ...ssword Press to advance to the clock calendar settings Use the buttons to change the month Press to advance Use the buttons to change the year Press to advance Use the buttons to change the other sett...

Page 10: ...he unit NODE number when used in MODBUS Network Press to advance to the input filter screen THE DIAGNOSTIC SCREEN The final menu item is DIAGNOSTICS This screen provides real time information about th...

Page 11: ..._________ Version ________________ Scaling Channel 1 Range _________ Channel 2 Range _________ Channel 3 Range _________ Channel 4 Range _________ Setup Password ___________ Log Interval ___________ C...

Page 12: ...tage is not present check the user supplied power supply or if using the 700 DPCF TPCF supply measure across terminals 24VDC and and If no 24VDC is present consult factory If 24VDC is present check fi...

Page 13: ...LEANED BEFORE RETURNING UNITS RETURNED UNCLEANED WILL BE CONSIDERED UNREPAIRABLE AND RETURNED TO SENDER OR DISCARDED NOTE DO NOT SUBMERGE UNITS FOR CLEANING WITH CABLE CUT OR REMOVED THIS WILL ALLOW C...

Reviews: