- 19 -
(8) Factory
defaults
The controller allows returning to standard settings set by the producer by
choosing [Prod] and pressing OK button. After activating this function, the
controller sets each parameter showed in the table.
(9) Output
testing
To make checking the controller work easier, it is possible to test output circuits
which control the fan and the pump, and the additional boiler launching system.
This function is available in service mode, only if the control process is off, i.e.
the controller was in STOP mode before switching to service mode. By
choosing [outP] on the display and pressing OK button you can turn on the
central heating pump for a while, by choosing [out
Π
] and pressing OK you can
turn on the fan and by choosing [outr] and pressing OK you can turn the
additional boiler on (if the additional module is connected). Choosing [outu]
allows testing the hot water pump output.
(10) Exiting service mode
By choosing [End] option on the display and pressing OK button you can exit
parameter setting mode.
The controller also exits service mode, when no buttons are pressed for 1
minute.
6.2.6)
Additional functions
To improve comfort in heated rooms, the controller has been equipped with an
input that allows connecting any kind of room thermostat with contact output.
When temperature in the room is below desired temperature, the central
heating pump is turned on and the room thermostat indicator is lit.
It means that the boiler should keep temperature set by the room thermostat
knob. After reaching desired temperature in the room, the room thermostat
indicator turns off, the central heating pump is turned off and the boiler switches
to mode in which it keeps burning at minimum temperature.
CAUTION
. In case of not having room thermostat in the system, the room thermostat input
contacts must be short-circuited.
6.2.7)
Controller failures
The controller is constantly testing if its internal circuits and temperature sensor
are working correctly. After detection of fault, it stops the fan, turns on the
central heating pump and shows proper error message on the display. In case
of failure please turn off the controller, plug the central heating pump to the
power source, ensure appropriate fuel firing in the boiler and contact the
service.