background image

5

Connecting the siren’s TAMPER to the Control Panel

At the “TAMPER” terminals, the Tamper contacts of the siren end up. When the siren is screwed 

to the wall and its lid is closed, this output is NC and becomes NO when the lid is opened or 

the siren detaches from the wall. These contacts can be connected to any perimeter or 24-hour 

zone of the panel (such as NC or EOL zone, using EOL resistor), taking care to use the correct 

polarity (COM & ZONE).
  
  

Caution!

   

If you use an EOL band, then, for greater security, place the EOL resistor in the siren,  

   

at the TAMPER ZONE output and in series with the cable as shown in the wiring 

  

diagram.

Power supply of the siren

The + 12V inputs are for powering the siren and charging the battery. They are connected to the 

corresponding outputs of the Control panel, taking care of the correct polarity.

  

Caution!

   

For the siren to function properly, a battery must be used. In the case, however, that  

   

you want the siren without battery to operate, you must connect the red battery cable 

   

to + 12V. The siren can operate this way, provided the cable’s cross-section allows it  

   

and the panel power supply  is able to provide the required current.

Selecting the activation method of the siren

The TRIGGER (+ or -) inputs are used to activate the siren. 

Activation can be done in two modes:

A. By positive voltage interruption

  Connect the “+ TRIGGER” input of the siren to the corresponding output of the Control Panel  

  or a programmable output (PGM), that provides 12.0V at standby mode and cut or turns to 0 V  

  when an alarm is given.
B. By negative voltage interruption

  Connect the “- TRIGGER” input of the siren to the corresponding output of the Control Panel  

  or a programmable output (PGM), that provides 0V at standby mode and become an Open  

  Collector or turns to 12.0 V when an alarm is given.

  

Note: 

 The siren follows the alarm duration of the Control panel. However, if the cables  

   

connected to the panel are interrupted or shorted, the siren activates an alarm for a  

   

maximum of 5 minutes.

TAMPER

COM | ZONE

FREE TAMPER SWITCH CONTACTS

12V

-      +

POWER SUPPLY INPUT (12V) FOR SIREN ΑΝD FOR BATTERY CHARGING 

TRIGGER

-      +

NEGATIVE OR POSITIVE ALARM ACTIVATION INPUT (PANEL CONTROLABLE)

Terminals Description

Summary of Contents for IRIS Lite

Page 1: ...1 Installation Manual IRIS Lite IRIS Basic Outdoor Self Powered Sirens ...

Page 2: ...2 ...

Page 3: ... cut off gives a five 5 minutes alarm if both the power supply cables and TRIGGER cable are cut off simultaneously It has short circuit protection on the battery charging of the cables output It has protection against faulty connection of the battery poles with simultaneous optical LED indication When the siren is in standby mode and its battery voltage drops bellow10 0 V flash stops flashing It h...

Page 4: ...d when the Trigger input has a 12VDC permanently It sounds an alarm if this voltage is inter rupted or when the voltage at this input is 5 8 V DC Activation from Trigger It is balanced when the Trigger input is permanently at 0 of the power supply and gives an alarm when the supply is cut off or when the input voltage is 1 5 V DC Operation Frequency 900 2700 Hz Acoustic Power 122dB at 1 meter Maxi...

Page 5: ... battery cable to 12V The siren can operate this way provided the cable s cross section allows it and the panel power supply is able to provide the required current Selecting the activation method of the siren The TRIGGER or inputs are used to activate the siren Activation can be done in two modes A By positive voltage interruption Connect the TRIGGER input of the siren to the corresponding output...

Page 6: ...ction terminals on page 5 and the following wiring diagram 6 When you finish cable connections connect the battery to the siren The siren can remain in this condition until you finish the installation The siren will start to operate normally only when supplied with power from the alarm control panel Note When the power supply is first applied from the panel to the siren a short sound will be heard...

Page 7: ... the one the siren will follow When all the LEDs are off the siren will have no lighting at standby mode Press MENU button to save settings Exit Setup To exit the programming procedure press continuously MENU button until the confirmation signal five BEEP is heard Immediately the siren will enter the standby mode The siren will also automatically exit programming and will return to standby mode af...

Page 8: ...The electrical and electronic equipment used must be handled separately and in accordance with the legislation which requires appropriate processing and recycling of the aforesaid goods The battery contains pollutants and therefore after the end of its lifetime it should not be disposed of in common waste but delivered to the appropriate operator for the collection and disposal of polluting waste ...

Reviews: