C-IPC 171
C-DIAS IPC WITH AMD FUSION G-T56N
Page 34
04.11.2019
15
STOP BRKPT
The CPU was stopped by a breakpoint
in the program.
INFO
16
CPU STOP
The CPU was stopped by the program-
ming software.
INFO
17
INT ERROR
The CPU has triggered a false interrupt
and stopped the user program or has
encountered an unknown instruction
while running the program.
Cause:
-
A nonexistent operating system
was used.
-
Stack error (uneven number of
PUSH and POP instructions).
-
The user program was interrupt-
ed by a software error.
Solution:
-
Correct programming error.
18
SINGLE STEP
The CPU is in single step mode and is
waiting for further instructions.
INFO
19
READY
A module or project has been sent to the
CPU and it is ready to run the program.
INFO
20
LOAD
The program is stopped and the CPU is
currently receiving a new module or
project.
INFO
21
UNZUL.
MODULE
The CPU has received a module that
does not belong to the project.
Solution:
-
Recompile and download the
entire project
22
MEMORY FULL
The operating system memory /Heap) is
too small. No memory could be reserved
while calling an internal or interface
function is called from the application.
Cause:
-
Memory is only allocated bun not
released.
Solution
-
Clear memory
23
NOT LINKED
When starting the CPU, a missing
module or a module that does not
belong to the project was detected.
Solution:
-
Recompile and download the
entire project
24
DIV BY 0
A division error has occurred.
Possible Causes:
-
Division by 0.
-
The result of a division does not
fit in the result register.
Solution:
-
Correct programming error.
25
DIAS ERROR
While accessing a DIAS module, an
error has occurred.
Hardware problem
26
WAIT
The CPU is busy.
INFO