CP 733
S-DIAS CPU UNIT
Page 12
06.12.2019
(1)
For USA and Canada:
The supply must be limited to:
a) max. 5 A at voltages from 0-20 V DC, or
b) 100 W at voltages from 20-60 V DC.
The limiting component (e.g. transformer, power supply or fuse) must be certified by an
NRTL (Nationally Recognized Testing Laboratory).
If several S-DIAS modules are connected, the total current of the S-DIAS
modules used must be determined and checked.
The total current of the +24 V supply on the S-DIAS bus cannot exceed
1.6 A!
The total current of the +5 V supply on the S-DIAS bus cannot exceed
1.6 A!
The specification for the current can be found in the module-specific docu-
mentation under "Electrical Requirements".