                                                                                               SIGMATEK FDD Step By Step Guide Size 5 to 9

STEP 8:  Run the motor

This step will provide instruction on how to set-up the basic drive parameters, perform  an auto-tune and run the 
motor in analog input terminal mode or keypad mode. 

Action

Detail

Power Up

Ensure:

The drive displays: inh (Enable terminal(s) is open)

Minimum and 
maximum speed

Enter:

Minimum speed Pr

01

 (Hz) 

Maximum speed Pr

02

 (Hz)

Accel and Decel 
rates

Enter:

Acceleration rate Pr

03

 (s)

Deceleration rate Pr

04

 (s)

Motor nameplate 
details

Ready to autotune

Autotune

The drive is able to perform either a stationary or a rotating autotune. The motor must be at 
a standstill before any autotune is enabled and disconnected from the load for a rotating 
autotune.

To perform an autotune:

Set  Pr

10 

to L2 

Go to Pr 

38

Set  Pr

38 

= 1 for a stationary autotune or set Pr

38

 = 2 for a rotating autotune

Close the drive enable signal (apply +24 V to terminal 11 or terminal 31 and 35 on 
FDD3. The drive will display ‘rdy’.

Give a Run command (apply +24 V to terminal 12 - Run forward or terminal 13 - 
Run reverse. The display will flash ‘tuning’ while the drive is performing the autotune.

Wait for the drive to display ‘inh’ and for the motor to come to a standstill. 

Remove the drive enable and run signal from the drive.

Ready to run (Analog input terminal mode by default)

Run

The drive is now ready to run the motor. Close Safe Torque Off (FDD3) and the Run Forward 
or Run Reverse terminals.

Increasing and 
decreasing speed

Changing the selected Analog frequency reference will increase and decrease the speed of 
the motor.

Stopping

To stop the motor by following the selected deceleration rate, open either the run forward or 
run reverse terminals. If the enable terminal is opened while the motor is running, the drive 
output is immediately disabled and the motor will coast to a stop.

Ready to run (Keypad mode)

Run

The drive is now ready to run the motor.  Set Pr 

05

 to 'PAd'.  Close Safe Torque Off (FDD3).

Press the start key 

Increasing and 
decreasing speed

Press the up and down keys 

 to increase and decrease the speed.

Stopping

Press the Stop/Reset key 

Motor rated current in Pr

06

 (Amps)

Motor rated speed in Pr

07

 (rpm / min

-1

)

Motor rated voltage in Pr

08

 (Volts)

Motor rated power factor in (cos 

) Pr

09

MOT. 3

LS 80 L   T

N   

734570 BJ  002    Kg  

9

40 C

S1

IP 55

I cl.F

V

Hz min kW 

cos 

-1

 

230 50 2800 0,75 0,83 0,3

1

2

3

4

Summary of Contents for FDD 3054.00270

Page 1: ...t is essential to read the control User Guide prior to using the SafeTorque O function in safety systems Section 4 6 Diese Anleitung bietet Informationen f r eine schnelle Inbetriebnahme eines einfach...

Page 2: ...1 Feature diagram PE DC DC U V W L1 L2 L3 6 5 5 1 41 42 2 3 4 77 8 9 DC BRAKE 8 10 11 13 7 8 9 12 5 1 2 7 U V W 5 12 12 12 12 9 10 8 12 1 1 2 3 13 11 4 5 6 7 6 5 Key 1 Rating label 2 Relay connection...

Page 3: ...eck model and voltage The model number can be found on the identification label on the top of the drive Please check that the model and the drive voltage range is suitable for the installation KIT BOX...

Page 4: ...m 1 18 in 0 mm 0 00 in 100 mm 4 0 in 100 mm 4 0 in 7 45 mm 1 77 in 30 mm 1 18 in 60 mm 2 37 in 100 mm 4 0 in 8 45 mm 1 77 in 30 mm 1 18 in 60 mm 2 37 in 100 mm 4 0 in 9 45 mm 1 77 in 60 mm 2 37 in 60...

Page 5: ...UL 508C A A A Input Output Input Output 05200250 31 40 40 10 8 06200330 48 8 63 60 16 4 06200440 56 6 63 70 25 3 05400270 29 40 35 6 8 05400300 29 40 35 6 8 06400350 36 63 40 10 6 06400420 46 63 50 16...

Page 6: ...kwise by approximately 30 2 Slide the terminal cover down 3 Remove terminal cover in direction shown Input phase conductor size Minimum ground conductor size 10 mm Either 10 mm or two conductors of th...

Page 7: ...ound terminals 2 0 N m 1 4 lb ft 6 Power and ground terminals 6 0 N m 4 4 lb ft 7 Power and ground terminals 12 N m 8 85 lb ft 8 and 9 Power and ground terminals 15 N m 11 1 lb ft A 1 2 2 1 2 1 2 1 2...

Page 8: ...inal block 2 is used for Motor connection On size 5 the supply and motor ground connections are made using the M5 studs located near the plug in power connector Refer to Figure 6 1 Optional heatsink m...

Page 9: ...ide Size 5 to 9 9 English Deutsch Figure 6 2 Size 6 power and ground connections On a size 6 the supply and motor ground connections are made using the M6 studs located above the supply and motor term...

Page 10: ...ize 5 to 9 Figure 6 3 Size 7 and 8 power and ground connections size 7 shown On size 7 and 8 the supply and motor ground connections are made using the M8 studs located by the supply and motor connect...

Page 11: ...5 to 9 11 English Deutsch Figure 6 4 Size 9A power and ground connections On size 9A the supply and motor ground connections are made using the M10 studs located by the supply and motor connection te...

Page 12: ...regulations The drive must be grounded by a connection capable of carrying the prospective fault current until the protective device fuse etc disconnects the AC supply The ground connections must be...

Page 13: ...TOP RESET the drive in keypad mode It can also be used to reset the drive in terminal mode ESCAPE Is used to exit from the parameter edit view mode rdy START Is used to start the drive in keypad mode...

Page 14: ...h tuning while the drive is performing the autotune Wait for the drive to display inh and for the motor to come to a standstill Remove the drive enable and run signal from the drive Ready to run Analo...

Page 15: ...he final drive run is not active Disabled The drive is stopped holding zero speed Enabled Supply loss condition has been detected Enabled The drive is applying dc injection braking Enabled The drive h...

Page 16: ...luated as suitable for use in surrounding air temperatures up to 40 C When the drive is through panel mounted the main terminal cover s must be removed in order to provide access to the mounting holes...

Page 17: ...tection does not provide branch circuit protection Branch circuit protection must be provided in accordance with the National Electrical Code NEC The Canadian Electrical Code and any additional local...

Page 18: ...dung 1 1 Anschlussdiagramm PE DC DC U V W L1 L2 L3 6 5 5 1 41 42 2 3 4 77 8 9 DC BRAKE 8 10 11 13 7 8 9 12 5 1 2 7 U V W 5 12 12 12 12 9 10 8 12 1 1 2 3 13 11 4 5 6 7 6 5 Legende 1 Typenschild 2 Relai...

Page 19: ...er tetyp und Spannung pr fen Den Ger tetyp finden Sie auf dem Identifikationsschild oben am Umrichter berpr fen Sie dass Ger tetyp und Spannungsbereich des Umrichters f r die Anwendung geeignet sind S...

Page 20: ...nstallationshandbuch Tabelle 3 1 enth lt die einzuhaltenden Abst nde Tabelle 3 1 Empfohlener Abstand Baugr e Abstand zwischen Umrichter und Schaltschrank EMV Filter Abstand zwischen Umrichtern Abstand...

Page 21: ...r gR UL Klasse CC J oder T IEC60364 5 52 mm UL 508C AWG A A A Eingang Ausgang Eingang Ausgang 05200250 31 40 40 10 8 06200330 48 8 63 60 16 4 06200440 56 6 63 70 25 3 05400270 29 40 35 6 8 05400300 29...

Page 22: ...ersinn 2 Schieben Sie die Klemmenabdeckung nach unten 3 Entfernen Sie die Klemmenabdeckung in der dargestellten Richtung Leitungsquerschnitt des Netzanschlusses Minimaler Leitungsquerschnitt der Erdve...

Page 23: ...mmen 6 0 N m 7 Strom und Erdanschlussklemmen 12 N m 8 und 9 Strom und Erdanschlussklemmen 15 N m A 1 2 2 1 2 1 2 1 2 1 3 2 B C D A Baugr en 5 bis 9 B Nur Baugr e 5 C Nur Baugr e 6 D Baugr en 7 bis 9 L...

Page 24: ...ird f r den Motoranschluss verwendet Bei Umrichtern der Baugr e 5 wird die Erdung von Netz und Motoranschluss durch die M5 Erdungsbolzen neben den Netzanschlussklemmen vorgenommen Siehe Abbildung 6 1...

Page 25: ...h Deutsch Abbildung 6 2 Baugr e 6 Strom und Erdungsanschl sse Bei Umrichtern der Baugr e 6 wird die Erdung von Netz und Motoranschluss durch die M6 Erdungsbolzen vorgenommen die sich ber den Netz und...

Page 26: ...gr en 7 und 8 Strom und Erdungsanschl sse Abbildung zeigt Baugr e 7 Bei Umrichtern der Baugr e 7 bis 8 wird die Erdung von Netz und Motoranschluss durch die M8 Erdungsbolzen vorgenommen die sich ber d...

Page 27: ...utsch Abbildung 6 4 Baugr e 9A Leistungswerte und Erdverbindungen Bei Umrichtern der Baugr e 9A wird die Erdung von Netz und Motoranschluss durch die M10 Erdungsbolzen vorgenommen die sich ber den Net...

Page 28: ...Umrichter muss so geerdet werden dass ein eventuell auftretender Fehlerstrom so lange abgeleitet wird bis eine Schutzeinrichtung Sicherung usw die Netzspannung abschaltet Die Erdungsanschl sse m ssen...

Page 29: ...bestimmten Parameters oder zur Bearbeitung von Parameterwerten STOPP RESET des Umrichters im Tastaturmodus Kann auch zum R cksetzen des Umrichters im Modus f r Klemmen ansteuerung verwendet werden Sta...

Page 30: ...24 V an Klemme 12 Rechtslauf oder Klemme 13 Linkslauf Am Display blinkt tuning w hrend der Umrichter die automatische Abstimmung durchf hrt Warten Sie bis der Umrichter inh angezeigt und der Motor zum...

Page 31: ...ert ist Deaktiviert Der Umrichter ist gestoppt wird auf Nulldrehzahl gehalten Freigegeben Es wurde ein Verlust der Stromversorgung erfasst Freigegeben Die Gleichstrombremsung ist aktiv Freigegeben Ein...

Page 32: ...eckmontage sind die Umrichter f r Umgebungstemperaturen bis 40 C geeignet Bei Umrichtern in Durchsteckmontage m ssen die Klemmenabdeckungen unten entfernt werden damit der Zugang zu den Montagebohrung...

Page 33: ...triebsanleitung Steuereinheit entnommen werden Damit der Motorschutz ordnungsgem arbeitet muss der Motornennstrom in Pr 06 oder Pr 05 007 eingegeben werden Der berlastschutz kann auch unterhalb von 15...

Page 34: ...0478 0637 04...

Reviews: