background image

 

Rev 1.5 

SignalFire Telemetry 

 

10

 

 

 

Modbus Register Map  

Technical Support and Contact Information 

SignalFire Telemetry 
140 Locke Dr, Suite B 
Marlborough, MA, 01752 
(978) 212-2868 

support@signal-fire.com

 

Revision History

 

Register 

Address 

Register 
Number 

Description 

Function

 

Code

 

Register 

Type 

Coils (0xxxx) 

Write-only 

101 

00102 

Relay1 Coil 

05 

Write Only 

102 

00103 

Relay2 Coil 

05 

Write Only 

111 

00112 

Counter1 Reset Coil 

05 

Write Only 

112 

00113 

Counter2 Reset Coil 

05 

Write Only 

Holding Registers (4xxxx) 

121 

40122 

Relay1 Pulse (0 = Off, 1 

 65,535 = Pulse Time (sec)) 

06 

Write Only 

122 

40123 

Relay2 Pulse 

06 

Write Only 

1100 

41101 

AI1: Voltage Reading (Unsigned int, mV) 

03, 04 

Read Only 

1101 

41102 

DI1: State (Unsigned int, 1 = Closed or 0 = Open) 

03, 04 

Read Only 

1102 

41103 

DI2: State 

03, 04 

Read Only 

1103 

41104 

Relay #1 State (Unsigned int, 1 = ON or 0 = OFF) 

03, 04 

Read Only 

1104 

41105 

Relay #2 State 

03, 04 

Read Only 

1105 

41106 

AI1: Scaled Reading (Float High Word) 

03, 04 

Read Only 

1106 

41107 

AI1: Scaled Reading (Float Low, Word) 

03, 04 

Read Only 

1107 

41108 

DI1: Total Counts (Unsigned int, High Word) 

03, 04 

Read Only 

1108 

41109 

DI1: Total Counts (Unsigned int, Low Word) 

03, 04 

Read Only 

1109 

41110 

DI2: Total Counts (Unsigned int, High Word) 

03, 04 

Read Only 

1110 

41111 

DI2: Total Counts (Unsigned int, Low Word) 

03, 04 

Read Only 

1111 

41112 

DI1: Average Frequency (Hz x 10) 

03, 04 

Read Only 

1112 

41113 

DI1: Instantaneous Frequency (Hz x 10) 

03, 04 

Read Only 

1113 

41114 

DI1: Counts per minute (x 10) 

03, 04 

Read Only 

1114 

41115 

DI2: Average Frequency (Hz x 10) 

03, 04 

Read Only 

1115 

41116 

DI2: Instantaneous Frequency (Hz x 10) 

03, 04 

Read Only 

1116 

41117 

DI1: Counts per minute (x 10) 

03, 04 

Read Only 

Revision 

Date 

Changes/Updates 

1.0 

7/25/2019 

Initial release 

1.1 

10/15/2019 

Frequency register description 

1.2 

11/26/2019 

Corrected mechanical drawings 

1.3 

1/16/2020 

Corrected part number 

1.4 

3/5/2020 

Minor corrections 

1.5 

4/24/2020 

Added detail on mirror mode 

Summary of Contents for Wireless I/O Module Mini

Page 1: ...tal I O to a SignalFire Gateway or mirror the digital I O wirelessly another Wireless I O Mini Module acting as a wire replacement The SignalFire Wireless I O Module Mini has the following features 1 Analog input 1 5V 2 Digital inputs 2 Relay outputs 2 SPDT Wide range DC power input 6 36 VDC Low power consumption DIN rail mount with pluggable screw terminal blocks Status LEDs ...

Page 2: ... Analog Input 0 5V Signal 10V Max Digital Inputs Dry Contact or 30 Volts Max push pull 2kHz maximum frequency Digital Outputs 2 SPDT s max 30 VDC 2 Amps 250 VAC 0 25 Amps Radio Frequency Compliance 902 928MHz ISM Band FHSS radio RP SMA connector FCC and IC Certified Contains FCC ID W8V SFTS500 IC 8373A SFTS500 Certified for use in Class I Division 2 Groups A B C D Temperature Code T5 ...

Page 3: ...ISSEMENT RISQUE D EXPLOSION La substitution de composants peut rendre ce materiel inacceptable pour les emplacements de classe I division 2 WARNING EXPLOSION HAZARD Do not disconnect while circuit is live unless area is known to be nonhazardous AVERTISSEMENT RISQUE D EXPLOSION Ne débranchez pas lorsque le circuit est en direct sauf si la zone est connue pour être nonhazardous WARNING The Wireless ...

Page 4: ...input terminal to ground to convert the signal to 1 5V 1 5V Signal GND 4 20mA Signal GND A Input 1 A Input 1 Digital Inputs The digital inputs 2 total can be dry contact or voltage must be push pull and pull to ground 30 Volts max Be sure to connect the ground bus from the module to either the ground of the voltage device or the dry contact The digital inputs report their current state as well as ...

Page 5: ...tatus LED also indicates the signal strength between it and its module pair In addition there are TX RX LEDs to indicate radio messages to from the module The status LED will blink once a second if it is not connected to another module If the node is connected to its paired module it will blink a link quality code every 3 seconds 3 Blinks Strong Signal 2 Blinks Good Signal 1 Blink Weak Signal Each...

Page 6: ...ll WIOM Minis on the network must be set to Node and they will communicate with a SignalFire Gateway For Point to Point set one WIOM Mini to Gateway and one WIOM Mini to Node on a network that has no other devices Node Mode In Node mode the WIOM Mini will send its analog and digital inputs outputs to the Gateway All IO and then be read set from a PLC via Modbus Node Mode The Gateway reads all inpu...

Page 7: ...put the analog input is not used Point to Point Mode Inputs from one module are mirrored as outputs on the other When set to Point to Point mode the WIOM Minis will not be viewable through a SignalFire Gateway as they will be on their own network The module that is set to Gateway will be locked to Slave ID 1 WIOM Mini to WIOM Mode A WIOM Mini and a regular WIOM can also operate in Point to Point m...

Page 8: ...ave the same Radio Network Radio Network Group and Corporate ID Encryption Key as the Gateway For two Wireless I O Module Minis to communicate in Point to Point mode they must share the same Radio Network Radio Network Group and Corporate ID Encryption but not share those settings with any other SignalFire network To use an Encryption Key in lieu of a Corporate ID check off the Enable Encryption b...

Page 9: ...ire Gateway If used this timeout must be set higher than the Modbus coil write frequency of the Modbus master device This option is available for both Point to Point and Node mode Analog Scaling Node Mode only Analog scaling can be used to scale an analog input to engineering units For example for a 0 1000psi sensor set the scale low to 0 and scale high to 1000 The scaled value will now be display...

Page 10: ...04 41105 Relay 2 State 03 04 Read Only 1105 41106 AI1 Scaled Reading Float High Word 03 04 Read Only 1106 41107 AI1 Scaled Reading Float Low Word 03 04 Read Only 1107 41108 DI1 Total Counts Unsigned int High Word 03 04 Read Only 1108 41109 DI1 Total Counts Unsigned int Low Word 03 04 Read Only 1109 41110 DI2 Total Counts Unsigned int High Word 03 04 Read Only 1110 41111 DI2 Total Counts Unsigned i...

Reviews: