Document Reference: X-0036-01-07 Cadmus & Ratifi Operating Manual
Drawn: 13/11/2020
Page 17 of 66
1.9.5.1
Counter Mode Configuration
Parameter Name
Description
Options
ELECTRICAL HIGH
Maximum counts per “Store Rate” period.
0 to 65535, integer value.
*note 1
ELECTRICAL LOW
Minimum c
ounts per “Store Rate” period.
0 to 65535, integer value
*note 1
ENGINEERING HIGH
Engineering value equating to “ELECTRICAL HIGH” counts.
Decimal number.
ENGINEERING LOW
Engineering value equating to “ELECTRICAL LOW” count.
Decimal number.
ENGINEERING UNITS
Unit associated with the engineering value. e.g. kWh
Maximum 5 characters.
*Note 1:
Maximum input frequency 1kHz.
When selecting the “store rate” for the device ensure, the electrical counts do not exceed 65535, and the maximum frequency d
oes not exceed 1kHz.
Example: To monitor power consumption, if the “store rate” is set to 60 minutes, this means the counts cannot exceed 65535 c
ounts in 60 minutes.
1.9.5.2
Interrupt Mode Configuration
Parameter Name
Description
Options
INTERRUPT FORCES UPLOAD
When OFF discrete is sampled every 60 seconds.
When ON discrete is sample every 60 seconds, and forces upload
then interrupt status is changed.
OFF, ON
INTERRUPT EDGE
Only visible when “INTERRUPT FORCES READ AND UPLOAD” = ON.
Determines what interrupt states cause upload.
FALLING EDGE, RISING EDGE, BOTH EDGES.