Signet 8059 External relay module 

2

4. Power

OUTPUT 24VDC 

+         - 

AC INPUT 

N L 

AC Power terminals

100 - 240 VAC
50/60 Hz, 20 VA

24 VDC Regulated,
300 mA maximum

DC OUTPUT 

+         - 

DC INPUT 

-     + 

DC Power terminals 

12 to 24 VDC

100 mA maximum

Pass-through DC

(less 0.7 VDC)

3. Installation

Tilt top of the 8059 to insert under top DIN rail, then press bottom 
of 8059 until the locking pin snaps onto lower DIN rail.

Removal

Insert screwdriver into release mechanism on bottom of 8059.
Pull down on release while lifting 8059 away from the DIN rail.

• 

This unit must be installed inside a protected panel.

• 

Always connect          to earth ground.

• 

Disconnect power before wiring.

• 

Do not install where persons may inadvertently come in 
physical contact with the terminals.

• 

Include protection devices in the power system in case of 
power supply malfunction. A very high voltage may occur at 
output terminals during failure.

• 

Do not touch immediately after removing power. Some 
surface areas may be very hot.

• 

Do not exceed temperature specifi cations.

• 

Do not store or operate the AC power supply in any 
environment subjected to vibrations or shock.

WARNING

NC     C     NO

RELAY A

NC     C     NO

RELAY B

NC     C     NO

RELAY C

NC     C     NO

RELAY D         

+  

S

3

L

   -

+  

S

3

L

   -

OUTPUT 24VDC

+         -

AC INPUT

INPUT

PASS-THRU

L    N  

COM

32:(5

Signet 3-8059 Relay Module

Test A

Test B

Test C

Test D

Relay A

Relay B

Relay C

Relay D

 LISTED
E171559

®

Summary of Contents for 8059

Page 1: ...s product should only be used for the purposes and in the manner described in this manual This unit must be installed on a DIN rail Dimensions Noryl is a registered trademark of GE Plastics 100 240 V 50 60 Hz 20 VA NC C NO RELAY A NC C NO RELAY B NC C NO RELAY C NC C NO RELAY D S3 L S3 L OUTPUT 24VDC AC INPUT INPUT PASS THRU L N COM 32 5 Signet3 8059RelayModule Test A Test B Test C Test D Relay A ...

Page 2: ...ed panel Always connect to earth ground Disconnect power before wiring Do not install where persons may inadvertently come in physical contact with the terminals Include protection devices in the power system in case of power supply malfunction A very high voltage may occur at output terminals during failure Do not touch immediately after removing power Some surface areas may be very hot Do not ex...

Page 3: ...not exceed 122 m 400 ft Do not route I O cables in conduit containing AC power wiring Electrical noise may interfere with data signal Routing cable in grounded metal conduit will help prevent electrical noise and mechanical damage The sensor configuration must be reset before the host instrument will recognize a new S3 L device see Calibrate menu Reset Sensor Configuration in the 8250 Level Transm...

Page 4: ...0V 5A dry contact relays are controlled via the serial connection to the instrument Use NO normally open COM common and NC normally closed to control external equipment Normal Operation Green COM LED flickering rapidly Both relays are controlled by the host instrument 8 Ordering Information 3 8059 4 159 000 772 External 4 Relay Module 3 8059 4AC 159 000 773 External 4 Relay Module with power suppl...

Reviews: