Page 6 of 6
DocNo.DCP0001328 RnB 10/10/03 rev6
Output connections
Connecting a SVMP2-8 to the SigNET iX LS
Triggers of the SVMP2-8 are wired to whatever external
equipment will be used to trigger them (e.g. switched relay or fire interface).
Set Options to Non-monitored mode
Connecting a SVMP2-8 to the SS2n (Network station)
Set Options to Non-monitored mode
Only using one message channel.
If you are only using one channel of the SVMP2-8, connect audio+
and audio- of both message connectors in parallel. This will ensure that there is no audio fault reported on
the unused channel.
Specification
Storage capacity
2 messages, each of up to 120 seconds
Audio bandwidth
16kHz
Audio Output level
0dBm
Line Input sensitivity
0dBm (0.775V)
Power Supply Requirements
100mA @18-36 VDC, externally regulated.
Width
249mm
Height
41mm
Depth
159mm
(behind
front
panel)
Weight
2kg
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
SigNET Amplification & Control
Tower Road, Glover Estate, Washington, Tyne & Wear, NE37 2SH.
Tel: +44 (0) 191 417 4551
Fax: +44 (0) 191 417 0634