background image

-4-

Wiring

1. This equipment to be connected to an un- switched 
circuit only.

2. For exits with Master- Remote or Self-Diagnostics, 
refer to supplementary data sheet for wiring diagrams 
and additional instructions.

3. CAUTION: Damage to battery will occur if battery 
connector is connected to charger board for 
prolonged period of time without continuous AC 
power provided.

Inspection and Maintenance

Important Note: Emergency lighting systems 
should be tested as often as local codes require, 
or at least monthly, to a certain that all 
components are operational. Allow battery to 
charge 8 hours before initial testing, and 24 hours 
to fully charge battery.

1. Normal Operation: When unit is functioning 
properly, with AC power supplied, the Status light and 
exit lamp will be on.

2. To Test: Press manual test switch. Status light will 
turn off and exit lamp will remain on in DC mode.

Note: Turn off AC power and disconnect battery before 
servicing unit.

Battery Replacement

Remove fixture from J-Box. Locate battery wiring and
disconnect 2- pin polarized battery plug. Pry battery
out of cavity to release hook and loop fastener. Replace
battery, reconnect battery plug and replace fixture.

Power Module Replacement

Remove fixture from J-Box. Remove two #8-32 screws
to J-Box and remove Power Module Assembly from J-
Box.Disconnect wire nuts or push nut connectors to AC line 
inputs. To replace with new Power Module, reverse this 
sequence.

220  VFW Avenue, Grasonville, MD 21638

TEL: (410) 827-8300   Fax:(410)827- 8866

sales@signtexinc.com    www.signtexinc.com

Signtex  Inc

LIGHTING

BATTERY DIAGNOSTIC FUNCTIONS:

Microprocessor programmed to perform tests as follows:

Continuous

Monitoring w/ 1

Second Sampling

Lamp

Connections

Transfer switch

function

Test switch

indicator

function

Full 90 minute

emergency

operation test 

with test/ fail

and manual

report signal

Battery discharge

rate under 

full load

Battery

Connections

Every

28 Days

Every

12 Months

SELF- TEST DIAGNOSTIC FUNCTIONS 

STATUS

NORMAL FULL CHARGE
NORMAL FAST CHARGE
FAILED BATTERY
FAILED LAMP
FAILED TRANSFER
FAILED CHARGER

GREEN ON
ORANGE ON
RED FLASH FAST
GREEN FLASH
ORANGE FLASH
RED FLASH SLOW

LED DISPLAY

Series RPROBB & RPROAC

Rapier Open Face Die Cast LED System
Battery Backup & AC Models

03.15.03

Wiring Diagrams & Instructions

POWER 

MODULE

R

E

D

B

R

O

W
N

OUTPUT 2.4-5 VDC

E M E R G E N C Y  S I G N S

A C  F I X T U R E S

FIXTURE HOUSING

BLK

R

E

D

R E D

V

I

O

L

E

T

V I O L E T

B

R

O

W
N

B R O W N

Y

E

L

L

O

W

G

R

E

E

N

P

I

N

K

O

R

A

N

G

E

B

L

A

C

K

OUTPUT 2.4-5 VDC

RED

LAMP CIRCUIT BOARD

LAMP CIRCUIT BOARD

FIXTURE

GROUND

NEUTRAL

120-277 VAC 

B L A C K

W H I T E

G R E E N

GROUND

NEUTRAL

LINE

LINE

120-277 VAC 

B L U E

B R O W N

G R E E N

POLARIZED

CONNECTOR

TEST PANEL

DIAGNOSTICS INDICATOR

CHARGE LIGHT

TEST SWITCH

8-PIN POLARIZED

2-PIN POLARIZED

CONNECTOR

CONNECTOR

HOUSING

BA
TTER

Y

Summary of Contents for RPROAC Series

Page 1: ...ear gas or electric heaters Mount and secure exit sign at a location and height to avoid ready access and tampering by unauthorized persons Exception Floor proximity installations The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition Do not use this equipment for other than intended use IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS S...

Page 2: ...arp metal blade Drill 3 16 diameter holes at locations noted above For additional support drill out 2 additional 3 16 dia holes at left and right sides on center Locate back plate in position on wall and mark support holes install wall anchors for support screws 5 For battery backup models connect 2 pin polarized battery plug 6 Run LED lamp plug through backplate Attach back cover to j box with 2 ...

Page 3: ...ur 8 32 screws and detach two corner brackets and one lower bracket Retain all screws 3 Remove lens diffuser and place on scratch free surface LED panel and test panel assembly in battery backup models only can be left in place 4 Place sign face down on raised wooden blocks or other scratch free surface and carefully knock out selected chevron with hammer and small punch 5 Place upper edge of lens...

Page 4: ...Disconnect wire nuts or push nut connectors to AC line inputs To replace with new Power Module reverse this sequence 220 VFWAvenue Grasonville MD21638 TEL 410 827 8300 Fax 410 827 8866 sales signtexinc com www signtexinc com Signtex Inc LIGHTING BATTERY DIAGNOSTIC FUNCTIONS Microprocessor programmed to perform tests as follows Continuous Monitoring w 1 Second Sampling Lamp Connections Transfer swi...

Reviews: