-4-
Wiring
1. This equipment to be connected to an un- switched
circuit only.
2. For exits with Master- Remote or Self-Diagnostics,
refer to supplementary data sheet for wiring diagrams
and additional instructions.
3. CAUTION: Damage to battery will occur if battery
connector is connected to charger board for
prolonged period of time without continuous AC
power provided.
Inspection and Maintenance
Important Note: Emergency lighting systems
should be tested as often as local codes require,
or at least monthly, to a certain that all
components are operational. Allow battery to
charge 8 hours before initial testing, and 24 hours
to fully charge battery.
1. Normal Operation: When unit is functioning
properly, with AC power supplied, the Status light and
exit lamp will be on.
2. To Test: Press manual test switch. Status light will
turn off and exit lamp will remain on in DC mode.
Note: Turn off AC power and disconnect battery before
servicing unit.
Battery Replacement
Remove fixture from J-Box. Locate battery wiring and
disconnect 2- pin polarized battery plug. Pry battery
out of cavity to release hook and loop fastener. Replace
battery, reconnect battery plug and replace fixture.
Power Module Replacement
Remove fixture from J-Box. Remove two #8-32 screws
to J-Box and remove Power Module Assembly from J-
Box.Disconnect wire nuts or push nut connectors to AC line
inputs. To replace with new Power Module, reverse this
sequence.
220 VFW Avenue, Grasonville, MD 21638
TEL: (410) 827-8300 Fax:(410)827- 8866
sales@signtexinc.com www.signtexinc.com
Signtex Inc
LIGHTING
BATTERY DIAGNOSTIC FUNCTIONS:
Microprocessor programmed to perform tests as follows:
Continuous
Monitoring w/ 1
Second Sampling
Lamp
Connections
Transfer switch
function
Test switch
indicator
function
Full 90 minute
emergency
operation test
with test/ fail
and manual
report signal
Battery discharge
rate under
full load
Battery
Connections
Every
28 Days
Every
12 Months
SELF- TEST DIAGNOSTIC FUNCTIONS
STATUS
NORMAL FULL CHARGE
NORMAL FAST CHARGE
FAILED BATTERY
FAILED LAMP
FAILED TRANSFER
FAILED CHARGER
GREEN ON
ORANGE ON
RED FLASH FAST
GREEN FLASH
ORANGE FLASH
RED FLASH SLOW
LED DISPLAY
Series RPROBB & RPROAC
Rapier Open Face Die Cast LED System
Battery Backup & AC Models
03.15.03
Wiring Diagrams & Instructions
POWER
MODULE
R
E
D
B
R
O
W
N
OUTPUT 2.4-5 VDC
E M E R G E N C Y S I G N S
A C F I X T U R E S
FIXTURE HOUSING
BLK
R
E
D
R E D
V
I
O
L
E
T
V I O L E T
B
R
O
W
N
B R O W N
Y
E
L
L
O
W
G
R
E
E
N
P
I
N
K
O
R
A
N
G
E
B
L
A
C
K
OUTPUT 2.4-5 VDC
RED
LAMP CIRCUIT BOARD
LAMP CIRCUIT BOARD
FIXTURE
GROUND
NEUTRAL
120-277 VAC
B L A C K
W H I T E
G R E E N
GROUND
NEUTRAL
LINE
LINE
120-277 VAC
B L U E
B R O W N
G R E E N
POLARIZED
CONNECTOR
TEST PANEL
DIAGNOSTICS INDICATOR
CHARGE LIGHT
TEST SWITCH
8-PIN POLARIZED
2-PIN POLARIZED
CONNECTOR
CONNECTOR
HOUSING
BA
TTER
Y