170
007-4653-001
11: D-brick2
Table 11-2 shows the power requirements and specifications of the D-brick2.
Table 11-2
D-brick2 Power Specifications
Specification
Value
Voltage range for rack
200-240 VAC
Voltage range selection
Automatic
Frequency
50-60 Hz
Power factor
>0.98
Maximum power consumption
700 VA
Typical power consumption
400 VA or less
Inrush current (25
°
C [77
°
F]
cold-start 1 PSU)
100 A maximum peak for 4 ms, 25 A thereafter at
maximum voltage
Harmonics
Meets EN61000-3-2
Power cord:
Cord type
Plug
Socket
SV or SVT, 18 WG minimum, 3 conductor
250 V, 10 A
IEC 320 C-14, 250 V, 15 A
Summary of Contents for Origin 3900