Technical and Environmental Specifications
007-4653-001
171
Table 11-3 provides temperature and humidity requirements for the D-brick2.
Table 11-4 provides additional environmental specifications for the D-brick2.
Table 11-3
D-brick2 Ambient Temperature and Humidity Requirements
Factor
Temperature
Relative Humidity
Maximum
Wet Bulb
Operating temperature
5
°
C to 40
°
C
(41
°
F to 104
°
F)
20% to 80% noncondensing
23
°
C
(73
°
F)
Non-operating temperature
0
°
C to 50
°
C
(32
°
F to 122
°
F)
8% to 80% noncondensing
27
°
C
(80
°
F)
Storage temperature
1
°
C to 60
°
C
(34
°
F to 140
°
F)
8% to 80% noncondensing
29
°
C
(84
°
F)
Shipping temperature
-40
°
C to +60
°
C
(-40
°
F to 140
°
F)
5% to 100% nonprecipitating
29
°
C
(84
°
F)
Table 11-4
D-brick2 Environmental Requirements
Environmental Factor
Requirement
Altitude, operating
0 to 3047 m (0 to 10,000 ft)
Altitude, non-operating
-305 to 12,192 m (-1000 to 40,000 ft)
Shock, operating
Vertical axis 5 g peak 1/2 sine, 10 ms
Shock, non-operating
30 g 10 ms 1/2 sine
Vibration, operating
0.21 grms 5-500 Hz random
Vibration, non-operating
1.04 grms 2-200 Hz random
Acoustics
Less than 6.0 B LwA operating at 20
°
C
Safety and approvals
CE, UL, cUL
EMC
EN55022 (CISPR22-A), EN55024 (CISPR24), FCC-A
Summary of Contents for Origin 3900
Page 1: ...SGI Origin 3900 Server User s Guide 007 4653 001 ...
Page 3: ...007 4653 001 iii Record of Revision Version Description 001 October 2003 Original Release ...
Page 4: ......
Page 12: ......
Page 18: ......
Page 62: ......
Page 65: ...Product Description 007 4653 001 39 Figure 2 1 512 processor Origin 3900 Server ...
Page 76: ......
Page 104: ......
Page 120: ......
Page 172: ......
Page 198: ......
Page 208: ......
Page 254: ......
Page 274: ......
Page 292: ......