PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: MESH-CEDRP is compatible with any qualifi ed Bluetooth mesh components and commissioning tools.
We recommend Silvair Commissioning as a reliable solution.
MESH-CEDRP
Plug-in Directional Passive Infra Red
(PIR) Occupancy Detector & Photocell
Input: 100-240 Vac 50/60Hz
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: sales@danlers.co.uk
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
11/10/19
INS374 MESH-CEDRP (Issue 03)
This directional MESH-CEDRP can plug into a
ceiling mounted socket (not included) - DANLERS
Product Code: MESH-CESO. The socket can
be mounted onto an appropriate BESA box
or pattress box. Confi gurable for any room
occupancy style, via the Silvair Platform (App
and Web).
INSTALLATION
To be installed by a competent person with
reference to BS 7671 or equivalent local standards.
If in doubt consult a qualifi ed electrician.
• Plan where the MESH-CEDRP is to be located
(see diagram 1). Switch off supply and check
for hidden cables and pipes.
• The MESH-CEDRP plugs into a ceiling mounted
socket (not included) - DANLERS Product Code:
MESH-CESO.
• The MESH-CEDRP should be connected as
shown in diagram 2:
L - Live in. N - Neutral in.
OPERATION
To check the operation of the MESH-CEDRP:
• Turn on the supply then after 20 seconds if the
sensor has recognised movement of a person
within its zone of detection the integral red LED
on MESH-CEDRP will stay illuminated for 4
seconds before the red LED turns off.
• Thereafter, every time movement is detected
by MESH-CEDRP the integral red LED will stay
illuminated for 4 seconds.
The control also features adjustable time out (time
lag) control and daylight threshold control which
are confi gured by the Silvair APP.
PRECAUTIONS
• Do not place the MESH-CEDRP near heat
sources, fans or in ventilated ceiling voids.
• MESH-CEDRP can be wired in parallel (sharing
the same Live and Neutral).
• Do not place close to, or positioned such
that, any light source points directly into the
MESH-CEDRP.
• Ensure wires and cables are securely held
within the connection terminals.
• The MESH-CEDRP should be protected by a 5
or 6 Ampere mcb or fuse.
•
Disconnect the MESH-CEDRP from the
circuit before performing insulation testing
of the wiring circuit.
DIAGRAM 1
5m
10m
Strong
Detection Zone
i.e. person
walking towards
the CEDR6P
Secondary
Detection Zone
i.e. person
walking across
the CEDR6P
60° 120°
Side elevation view
5m
10m
Strong
Detection Zone
i.e. person
walking towards
the CEDR6P
Secondary
Detection Zone
i.e. person
walking across
the CEDR6P
60° 120°
Plan view
L N
Ceiling Socket
(Not included)
DANLERS
Code:
MESH-CESO
L
N
Back box or
BESA box
MESH-CEDRP or
MESH-CEDRPLR
230Vac
5A or 6A MCB
or fuse
DIAGRAM 2
5 YEAR WARRANTY
MESH-CEDRP comes with a 5 year
warranty from the date of manufacture
and is CE marked.
TECHNICAL DETAILS
INPUT
Voltage:
100 - 240Vac
Frequency:
50/60Hz
Max. mains current:
20mA
Standby current:
14mA
RADIO TRANSCEIVER
Operating frequencies: 2.4... 2,483 GHz
Max. output power:
+4 dBm
LUX PARAMETERS
Range:
5 - 2000 lux
OPERATING CONDITIONS
Note: The temperature difference between the
detection target and the background must be
at least 4 °C.
Ambient temperature:
-20... +40 °C (lout
20mA)
Storage temperature:
-25... +75 °C
Max. relative humidity:
0... 80%, non cond.
CONNECTORS
Terminal block
Wire size:
0.5mm
2
- 2.5mm
2
solid or stranded
Wire strip length:
6-7mm
Tightening torque:
0,4 Nm/4 Kgf.cm
MECHANICAL DATA
Dimensions:
74mm x 90mm x
140mm (adjustable)
Weight:
172g (unpacked)
Degree of protection:
IP20
Protection class:
Built-in Class 2
Material (casing)
Flame-retardant
polycarbonate
Finish / Colour
Matt /White (RAL
9003)
Protection class:
Built-in Class 2
CONFORMITY AND STANDARDS
EMC emission:
EN 301 489-1 V2.2.0,
EN 301 489-17 V3.1.1,
EN 55032: 2015,
EN61000-3-2: 2014,
EN61000-3-3: 2013
EMC immunity:
EN 301 489-1 V2.2.0, EN 301 489-17 V3.1.1
Environment:
Complies with WEEE and RoHS directives
CB scheme:
IEC60669-1:1998,
IEC60669-1:1998/AMD1:1999,
IEC60669-1:1998/AMD2:2006,
IEC60669-2:2002,
IEC60669-2-1:2002/AMD1:2008,