Selection of power supply frequency to the valves (AC/DC)
1.
Make sure that the output frequency to the valves, selected by jumper [8], corresponds to the value indicated on
the coils (e.g. both are set to AC).
2.
Should the two frequencies be different, move the jumper [8] in order to select the same frequency as indicated
on the coils.
3.
Put the front panel back in place and fasten the 4 screws.
4.
Close the transparent cover by means of the two screws [21] (Optional).
Never select 115 or 230 V DC for output!
6.2
Parameters selection
Connecting the power supply [4]:
L = phase, N = neutral
On/off switch [1] on 1. The display [7] will indicate for 3 seconds the release code of Simatek GFC 16.
Once the codes disappear, the display will show letter E (run) and the number of the valve which is going to be
activated. LED OK [18] and REMOTE [35] are on.
1) Press SELECT MENU [9]:
1 will flash on display [7]:
Using keys “+/-” [10] select the No. of valves, you wish to connect.
Example: If you wish to connect 4 valves to Simatek GFC 16, select 4.
Should you skip this step of the MENU, Simatek GFC 16 will automatically
set No. of valves as if they were all connected (Simatek GFC 16:4) then 4
valves will be recognized, (Simatek GFC 16:12) then 12 valves will be
recognized.
2) Press SELECT MENU [9]:
2 will flash on display [7]:
Using keys “+/-” [10] select Pulse time (0.01 – 9.99 sec).
3) Press SELECT MENU [9]:
3 will flash on display [7]:
Using keys “+/-” [10] select Pause time (1 – 999 sec).
4) Press SELECT MENU [9]:
4 will flash on display [7]:
Using keys “+/-” [10] select No. of cycles of Shut down cleaning.
Select 0 if you do not wish to have shut down cleaning.
Pause time in Shut down cleaning is the same as the one selected at point 3).
5) Press SELECT MENU [9]:
E1 will flash on display [7] the cleaning cycle starts.
LED 1 [11] will indicate that a valve is activated.
LED 2 [12] will indicate that Simatek GFC 16 is waiting to activate the next
valve.
NOTE!
-
Valves are pulsed from output No. 1 onwards.
-
Check that during the first cleaning cycle every valve is activated.
-
We suggest setting the Simatek GFC 16 working parameters to clean the filter at
the lowest possible frequency, thereby reducing the little dust escape arising
during jet-pulsing, achieving a longer lifetime of filterbags/cartridges and
reducing the compressed air consumption.
-
Pause time should allow an efficient filter cleaning in worst conditions, but
should never be shorter than the time needed to re-pressurise the compressed-
air tank.
-
While selecting parameters (in Select menu), Simatek GFC 16 will return to
normal operation if no buttons are pressed within a 5 minutes interval.