72
EN
6.7
Water system treatment
When filling and restoring the system it is good practice to use
water with:
– appearance: clear
– pH: 6.5 - 8.5
– hardness: < 19.96°F
– the maximum content of chlorides allowed is 250 mg/l
– it is recommended that the total quantity of water to use, in-
cluding top-ups, with a total hardness of 20°F
DOES NOT
ex-
ceed 20 litres/kW
If the water hardness is more than 20°F, to calculate the total
quantity of water to use, use the formula: (20°F/hardness meas-
ured °F) x 20.
Example with water hardness of 25°F: (20/25) x 20 = 16 l/kW
If the water characteristics are different from those indicated,
it is advisable to use a safety filter on the water delivery pipe to
trap impurities, in addition to a chemical treatment system for
protection against possible deposits and corrosion which could
jeopardise the thermal unit’s operation.
NOTE:
the conversion factor between °dH (German degrees) and
°F (French degrees) is 0.56 (1°dH = 0.56 x °F).
m
CAUTION
– It is useful to note the quantities of water to fill the
system and top it up, and the values of the quality of
water used.
6.8
Plumbing connections
The dimensions of the water fittings of
Sime
SOLO HE EV
boilers
are given below.
M
CI
R
SC
A
G
H
D
I
B
E
C
SC
S
L
F
Fig. 32
Description
SOLO HE EV
25
35
A (mm)
1030
1130
B (mm)
16,5
16,5
C (mm)
39
39
D (mm)
470
470
E (mm)
39
39
F (mm)
80
80
G (mm)
395
395
H (mm)
370
370
I (mm)
265
265
W (mm)
90
90
M System delivery
G 1”
G 1”
R System return
G 1”
G 1”
CI System filling
G 1/2”
G 1/2”
S Outlet
G 1/2”
G 1/2”
SC Condensate outlet (Øe/Øi mm)
25 / 21
25 / 21
6.9
Fuel supply
The possible fuel supply circuits are shown in the following dia-
grams. To size the circuit, refer to the following tables.
Burner lower than the tank
Y
H = x-y
A
X
Fig. 33
H (m)
Lunghezza tubo (m)
Ø6 mm
Ø8 mm
Ø10 mm
0,5
19
60
100
1,0
21
66
100
1,5
23
72
100
2,0
25
79
100
2,5
27
85
100
3,0
29
91
100
3,5
31
98
100
a
WARNING
– X < 20 m
– A = Bottom valve, which must be kept as low as pos-
sible to prevent cavitation. In any case, Y < 4 m.
Burner higher than the tank
H
A
Fig. 34
Summary of Contents for 8103047
Page 2: ...2 ...
Page 6: ...6 IT ...
Page 12: ...12 IT ...
Page 24: ...24 IT ...
Page 45: ...45 IT ...
Page 46: ...46 EN ...
Page 50: ...50 EN ...
Page 56: ...56 EN ...
Page 68: ...68 EN ...
Page 89: ...89 EN ...
Page 93: ...93 EN IT ...
Page 94: ...94 EN IT ...
Page 95: ...95 ...