99
EN
6.4
List of parameters
The parameters PAR 01 and PAR 02 are factory set according to
table “A” and automatically generate the settings for parameters
PAR 04, PAR 08, PAR 18 and PAR 31 as shown in the table.
d
IT IS FORBIDDEN
Use settings other than those shown in the table “A” as
this could generate a serious boiler malfunction.
TABLE “A”
Type of
gas
G20
G31
B o i l e r
p o w e r
(kW)
80
116 160 200 240 280
80
116 160 200
PAR 01
1
2
3
4
5
6
50
51
52
53
PAR 02
5
5
5
5
5
5
5
5
5
5
PAR 04
5
5
5
5
5
5
5
5
5
5
PAR 08
33
33
33
33
45
25
28
33
41
40
PAR 18
30
30
30
72
72
72
30
30
30
72
PAR 31
100 100 100 100 100 100 100 100 100 100
TABLE “B”
No. Description
1
Instant monothermal – 3-way electric – DHW flowmeter
2
Instant monothermal – 3-way electric – DHW flowmeter –
solar input
3
Remote storage tank – 3-way electric – storage tank sensor –
low inertia
4
On-board storage tank – 3-way electric – DHW sensor – low
inertia
5
Storage tank – 3-way electric – storage tank thermostat – low
inertia (or heating only)
6
Remote storage tank – dual pump – storage tank sensor – low
inertia
7
On-board storage tank – dual pump – DHW sensor – low
inertia
8
Remote storage tank – dual pump – storage tank thermostat –
low inertia (or heating only)
9
Heating only – anti-freeze sensor – low inertia
10 Storage tank – 3-way electric – storage tank sensor – high
inertia
11 Storage tank – dual pump – storage tank sensor – high inertia
12 Storage tank – 3-way electric – storage tank thermostat – high
inertia or heating only high inertia
13 Storage tank – dual pump – storage tank thermostat – high
inertia
14 Heating only – anti-freeze sensor – high inertia
Type
No. Description
Range
U/M
Step
Default
CONFIGURATION
PAR
01 Combustion configuration
– = ND
1 .. 53
-
-
See table
“A”
PAR
02 Hydraulic configuration
– = ND
1 .. 14 (see table “A”)
-
-
See table
“B”
PAR
03 Assigning Timed Programmer 2
1 = DHW+Recirculation Pump
2 = DHW
3 = Recirculation Pump
-
-
1
PAR
04 Disabling Pressure Transducer
0 = Disabled
1 = Enabled 0…4 bar
2 = Enabled 0…6 bar
3 = Enabled 0…4 bar NO ALARM
4 = Enabled 0…6 bar NO ALARM
5 = Enabled 0.8…5.8 bar
6 = Enabled 0.3…5.8 bar
-
-
See table
“A”
PAR
05 Assigning Auxiliary Relay
1 = Remote alarm
2 = Recirculation Pump
3 = automatic filling
4 = N.C. remote alarm
5 = Heat pump
6 = Zone 2 valve
-
-
1
PAR
06 Disabling Light Bar
0 = Disabled
1 = Enabled
-
-
1
PAR
07 Assigning Channels QAA73
0 = Not assigned
1 = Circuit 1
2 = 3-zone system
-
-
1
PAR
08 No. of Ignition Step Fan Revs
0,0 …. 81
rpmx100
0.1 from
0.1 to
19.9
1 from
20 to 81
See table
“A”
PAR
09 Long chimney
0 … 40
%
1
0
PAR
10 Opentherm device
1 = QAA73
2 = QAA53
3 = RVS43.143
4 = RVS46.530
5 = RVS61.843
-
-
1
PAR
11 External Sensor Value Correction
-5...+5
°C
-
0
PAR
12 Duration of Backlighting
- - = always
0 = never
1…199
seconds
x 10
1
3
PAR
13 Modulating Pump Speed
- - = no modul.
AU = AUTO
30...100
%
10
AU